UMG 96-PA-MID+CH 90...277 V AC, 90...250 V DC
MID zertifiziert für Wirkenergie- Verrechnungszwecke in der Schweiz
Product description
4-in-1 energy management: | power quality monitoring | RCM monitoring | MID certification:
The UMG 96-PA energy measurement device can combine four functions in one device and can be modularly extended by two analog inputs - either as 0-20 mA analog inputs (e.g. DC measurement) or as RCM measurement inputs with cable break detection and additional temperature measurement. It is also MID certified and approved for active energy billing purposes:
Energy management system
- Continuous energy monitoring
- Identification of potential savings
- Reduction of energy costs
- Compliance with tax and regulatory requirements
Power quality
- Secure, highly available power supply
- Avoidance of production downtime
- Maximize uptime / preventive maintenance
- Avoidance of quality defects in the product
Residual current monitoring (RCM)
- Permanent monitoring of residual currents
- Supports fire and personal protection
- Reduced effort for DGUV V3 testing
- Increased system availability
General:
Measuring accuracy for voltage, current 0.2%
Measuring accuracy for active energy (kWh, .../5 A) class 0.2S
Supply voltage:
AC 90 V - 277 V (50/60) Hz or DC 90 V - 250 V, 300 V CAT III
Inputs and outputs:
3 digital inputs and outputs each
1 analog output
RMS value measurement - instantaneous values, e.g:
Current, voltage, frequency
Active, reactive and apparent power
Power factor
Energy measurement:
Active, reactive and apparent energy
Tariffs: HT / NT
Ambient conditions:
Temperature range, operation: K55 (-10 ... +55 °C)
Acquisition of average values, e.g:
Voltage, current / current and maximum
Active, reactive and apparent power / current and maximum
Frequency / current and maximum
Measurement of the voltage quality:
Harmonics per order / current and voltage: 1.-40.
Distortion factor THD-U /THD-I in %
Current and voltage, zero, positive and negative sequence
Measurement data recording:
4 MB memory (flash)
Average, minimum and maximum values
Interface / protocol:
RS485 / Modbus RTU
Programming / limit values / alarm management:
Comparator (2 groups with 3 comparators each)
Grid visualization software
Free GridVis Essentials
Optional additional functions with the GridVis Standard and Expert packages
Measurement voltage input (3 x):
Overvoltage category: 600 V CAT III
Measuring range, voltage L-N, AC (without transformer): 0 ... 600 Vrms (± 10%)
Measuring range, voltage L-L, AC (without transformer): 0 ... 1040 Vrms (± 10%)
Frequency measuring range: 45 ... 65 Hz
Sampling frequency per channel (50 / 60 Hz): 8.33 kHz
Measurement in quadrants: 4
Networks: TN, TT
Measuring current input (3 x):
Rated current: 1 / 5 A
Overvoltage category: 300 V CAT II
Sampling frequency: 8.33 kHz
Mechanical properties:
Protection class according to EN 60529 (with seal = IP54): Front IP40 / Rear IP20
Mounting according to IEC EN 60999-1 / DIN EN 50022: Front panel
Installation:
Built-in device, 96 x 96 x 86 mm (WxHxD)
Supply voltage: 90 - 277 V AC
Installation category: 300 V CAT III
Accessories (included):
Installation instructions
Safety instructions included
Mounting kit
RS485 terminating resistor 120 Ohm
Observe installation position and minimum distances according to installation instructions:
Top/bottom 50mm distance
Lateral distance 20mm