This range complements selected articles

Isolating current transformer KUW-1

Kabelumbau-Wandler bis 18 mm Durchmesser


Isolating current transformer KUW-2

Kabelumbau-Wandler bis 28 mm Durchmesser


Isolating current transformer KUW-4

Kabelumbau-Wandler bis 42 mm Durchmesser


MID+CH certified
J.52.32.005

UMG 96-PA-MID+CH 90...277 V AC, 90...250 V DC

4 MB Speicher, Modulares Energiemessgerät
MID zertifiziert für Wirkenergie- Verrechnungszwecke in der Schweiz

Product description

4-in-1 energy management: | power quality monitoring | RCM monitoring | MID certification:

The UMG 96-PA energy measurement device can combine four functions in one device and can be modularly extended by two analog inputs - either as 0-20 mA analog inputs (e.g. DC measurement) or as RCM measurement inputs with cable break detection and additional temperature measurement. It is also MID certified and approved for active energy billing purposes:


Energy management system

- Continuous energy monitoring

- Identification of potential savings

- Reduction of energy costs

- Compliance with tax and regulatory requirements


Power quality

- Secure, highly available power supply

- Avoidance of production downtime

- Maximize uptime / preventive maintenance

- Avoidance of quality defects in the product



Residual current monitoring (RCM)

- Permanent monitoring of residual currents

- Supports fire and personal protection

- Reduced effort for DGUV V3 testing

- Increased system availability



General:

Measuring accuracy for voltage, current 0.2%

Measuring accuracy for active energy (kWh, .../5 A) class 0.2S


Supply voltage:

AC 90 V - 277 V (50/60) Hz or DC 90 V - 250 V, 300 V CAT III


Inputs and outputs:

3 digital inputs and outputs each

1 analog output


RMS value measurement - instantaneous values, e.g:

Current, voltage, frequency

Active, reactive and apparent power

Power factor


Energy measurement:

Active, reactive and apparent energy

Tariffs: HT / NT


Ambient conditions:

Temperature range, operation: K55 (-10 ... +55 °C)


Acquisition of average values, e.g:

Voltage, current / current and maximum

Active, reactive and apparent power / current and maximum

Frequency / current and maximum


Measurement of the voltage quality:

Harmonics per order / current and voltage: 1.-40.

Distortion factor THD-U /THD-I in %

Current and voltage, zero, positive and negative sequence


Measurement data recording:

4 MB memory (flash)

Average, minimum and maximum values


Interface / protocol:

RS485 / Modbus RTU


Programming / limit values / alarm management:

Comparator (2 groups with 3 comparators each)


Grid visualization software

Free GridVis Essentials

Optional additional functions with the GridVis Standard and Expert packages


Measurement voltage input (3 x):

Overvoltage category: 600 V CAT III

Measuring range, voltage L-N, AC (without transformer): 0 ... 600 Vrms (± 10%)

 Measuring range, voltage L-L, AC (without transformer): 0 ... 1040 Vrms (± 10%)

Frequency measuring range: 45 ... 65 Hz

Sampling frequency per channel (50 / 60 Hz): 8.33 kHz

Measurement in quadrants: 4

Networks: TN, TT


Measuring current input (3 x):

Rated current: 1 / 5 A

Overvoltage category: 300 V CAT II

Sampling frequency: 8.33 kHz


Mechanical properties:

Protection class according to EN 60529 (with seal = IP54): Front IP40 / Rear IP20

Mounting according to IEC EN 60999-1 / DIN EN 50022: Front panel


Installation:

Built-in device, 96 x 96 x 86 mm (WxHxD)

Supply voltage: 90 - 277 V AC

Installation category: 300 V CAT III


Accessories (included):

Installation instructions

Safety instructions included

Mounting kit

RS485 terminating resistor 120 Ohm


Observe installation position and minimum distances according to installation instructions:

Top/bottom 50mm distance

Lateral distance 20mm


Read more
Downloadcenter
Shop
Contact