Residual Current Monitoring (RCM) (Type B)
- Report Instead of Shutting Down
- Maximum system availability
- Innovative measurement technology
- Safety in all areas
For systems rated at more than 500 A, use only shielded current transformers.
At this current level and above, interference from conductors that are not properly aligned and centered within the current transformer becomes increasingly significant, resulting in less accurate measurement results. The shielded current transformer prevents this magnetic interference.
- Monitoring of fault and leakage currents, as well as insulation resistance
- Early warning
- Predictive maintenance of systems
- Monitoring of neutral conductors for overload caused by harmonic distortion
- Monitoring of fire-hazardous currents in fire-prone facilities
Definitions:
RCM – Residual Current Monitor
These devices monitor residual currents in electrical systems, display the current value, and signal when threshold values are exceeded.
RCMA & RCMB
Bender designation for Type B residual current monitoring devices in accordance with IEC 60755 for monitoring alternating currents, pulsating and smooth DC fault currents.
RCMS
Bender designation for multi-channel residual current monitoring systems of Types A and B in accordance with IEC 60755 for monitoring alternating currents, pulsating, and smooth DC fault currents.
MRCDB – Modular Residual Current Devices
Their function is to trip a circuit breaker within a specified time if the residual current exceeds a certain value. They enable circuit breakers to be supplemented for personal safety and fire protection.
In grounded power supply systems, such as TN/TT systems, the insulation resistance is indirectly determined by the magnitude of the fault current. Here, residual current monitors (RCMs) are used to monitor an electrical system or circuit for a potential fault current or residual current (figure above). An alarm is triggered when the fault current exceeds a specified value. The RCM should be set so that the alarm is triggered before the automatic shutdown required by standards occurs.
Filter
Reset filterResidual Current Monitoring (RCM) (Type B)
- Report Instead of Shutting Down
- Maximum system availability
- Innovative measurement technology
- Safety in all areas
For systems rated at more than 500 A, use only shielded current transformers.
At this current level and above, interference from conductors that are not properly aligned and centered within the current transformer becomes increasingly significant, resulting in less accurate measurement results. The shielded current transformer prevents this magnetic interference.
- Monitoring of fault and leakage currents, as well as insulation resistance
- Early warning
- Predictive maintenance of systems
- Monitoring of neutral conductors for overload caused by harmonic distortion
- Monitoring of fire-hazardous currents in fire-prone facilities
Definitions:
RCM – Residual Current Monitor
These devices monitor residual currents in electrical systems, display the current value, and signal when threshold values are exceeded.
RCMA & RCMB
Bender designation for Type B residual current monitoring devices in accordance with IEC 60755 for monitoring alternating currents, pulsating and smooth DC fault currents.
RCMS
Bender designation for multi-channel residual current monitoring systems of Types A and B in accordance with IEC 60755 for monitoring alternating currents, pulsating, and smooth DC fault currents.
MRCDB – Modular Residual Current Devices
Their function is to trip a circuit breaker within a specified time if the residual current exceeds a certain value. They enable circuit breakers to be supplemented for personal safety and fire protection.
In grounded power supply systems, such as TN/TT systems, the insulation resistance is indirectly determined by the magnitude of the fault current. Here, residual current monitors (RCMs) are used to monitor an electrical system or circuit for a potential fault current or residual current (figure above). An alarm is triggered when the fault current exceeds a specified value. The RCM should be set so that the alarm is triggered before the automatic shutdown required by standards occurs.
