Shop
RCM420CH-DM1C-2 Differenzstrom Überwachungsgerät
Type A according to IEC 60755
Tripping current range: 10 mA – 10 A
For TN/TT systems
Special Swiss firmware
When used with electrical or electronic loads that include a DC component, a solution sensitive to all current types—such as the RCMA423 or an equivalent device—must always be implemented.
· Version with spring clamp
· Classification according to IEC 60755 – Type A
· Power system: TN / TT systems
· Special firmware suitable for Swiss applications
· Supply voltage: 70 ... 300 V AC/DC
· Measurement channels: 1
· Differential currents: AC + pulsating DC
· Rated frequency: 42 ... 2000 Hz
· Response value I n1: 50 ... 100 %
· Threshold value I n2: 10 mA ... 10 A
· Main alarm relay: 1 changeover contact
· Early warning alarm relay: 1 changeover contact
· Dimensions: W 36 x H 90 x D 70.5 mm
with option M1C
Analog output 0/4…20 mA (without galvanic isolation),
one changeover contact as a freely configurable alarm signal
Shielded transducers are recommended for load currents of 500 A or higher.