MID+CH certified
J.52.32.005

UMG 96-PA-MID+CH 90...277 V AC, 90...250 V DC

8 MB Speicher, Modulares Energiemessgerät MID zertifiziert für Wirkenergie- Verrechnungszwecke in der Schweiz

4-in-1: Energy Metering, Power Quality, RCM, MID

MID-certified for billing purposes

Active energy Class 0.2S, current/voltage 0.2%

RS485 Modbus RTU and 8 MB data memory

4-in-1 Energy Management: | Power Quality Monitoring | RCM Monitoring | MID Certification:

The UMG 96-PA energy meter combines four functions in a single device and can be expanded modularly with two analog inputs—either as 0–20 mA analog inputs (e.g., DC measurement) or as RCM measurement inputs with cable break detection and additional temperature measurement. It is also MID-certified and approved for active energy billing purposes:


Energy Management System


· Continuous energy monitoring

· Identification of savings opportunities

· Reduction of energy costs

· Compliance with tax and regulatory requirements


Power Quality


· Reliable, high-availability power supply

· Prevention of production downtime

· Maximizing uptime / preventive maintenance

· Prevention of product quality defects


Residual Current Monitoring (RCM)


· Continuous monitoring of residual currents

· Supports fire and personal safety

· Reduced effort for DGUV V3 inspections

· Increased system availability

General:


· Measurement accuracy for voltage and current: 0.2%

· Measurement accuracy for active energy (kWh, .../5 A): Class 0.2S


Supply voltage:


· AC 90 V – 277 V (50/60) Hz or DC 90 V – 250 V, 300 V CAT III


Inputs and Outputs:


· 3 digital inputs and 3 digital outputs each

· 1 analog output


RMS measurement – instantaneous values, e.g.:


· Current, voltage, frequency

· Active, reactive, and apparent power

· Power factor


Energy measurement:


· Active, reactive, and apparent work

· Rates: High Voltage / Low Voltage


Environmental conditions:


· Temperature range, operation: K55 (-10 ... +55 °C)


Recording of average values, e.g.:


· Voltage, current / current and maximum

· Active, reactive, and apparent power / current and maximum

· Frequency / current and maximum


Power quality measurement:


· Harmonics by order / current and voltage: 1st–40th

· Total harmonic distortion (THD-U / THD-I) in %

· Current and voltage, zero-sequence, positive-sequence, and negative-sequence


Measurement data logging:


· 8 MB memory (flash)

· Average, minimum, and maximum values


Interface / Protocol:


· RS485 / Modbus RTU


Programming / Threshold Values / Alarm Management:


· Comparators (2 groups, each with 3 comparators)


Grid visualization software


· Free GridVis Essentials

· Optional additional features with the GridVis Standard and Expert packages


Measurement voltage input (3 x):


· Voltage category: 600 V CAT III

· Measurement range, voltage L-N, AC (without transformer): 0 ... 600 Vrms (± 10%)

· Measurement range, voltage L-L, AC (without transformer): 0 ... 1040 Vrms (± 10%)

· Frequency measurement range: 45 ... 65 Hz

· Sampling frequency per channel (50 / 60 Hz): 8.33 kHz

· Measurement in quadrants: 4

· Power systems: TN, TT


Current measurement input (3 x):


· Rated current: 1 / 5 A

· Overvoltage category: 300 V CAT II

· Sampling frequency: 8.33 kHz


Mechanical characteristics:


· Protection class according to EN 60529 (with gasket = IP54): Front IP40 / Rear IP20

· Mounting per IEC EN 60999-1 / DIN EN 50022: Panel mounting


Installation:


· Flush-mounted unit, 96 x 96 x 86 mm (WxHxD)

· Supply voltage: 90–277 V AC

· Installation category: 300 V CAT III


Accessories (included):


· Installation instructions

· Includes safety instructions

· Mounting kit

· RS485 terminating resistor, 120 ohms


Follow the installation instructions regarding mounting orientation and minimum clearances:


· 50 mm clearance above and below

· 20 mm clearance on the sides