Why does a residual current circuit breaker trip even though there is no fault?
High leakage currents often occur in modern industrial plants. These are operational and not a defect. The RCD only measures the differential current. If this exceeds the limit value, it switches off. The cause is usually not an insulation fault, but the sum of the leakage currents.
What exactly does a residual current device measure?
The RCD compares the current in the incoming and outgoing conductors. If the difference is too great, current flows through the earth. It does not distinguish between fault current and leakage current. The only decisive factor is the magnitude of the differential current.
Why does this problem occur particularly with frequency converters?
Frequency converters generate steep voltage edges. EMC filters divert interference to earth. In addition, long, shielded motor cables have a capacitive effect. This results in stationary and variable leakage currents, which can add up and trigger the residual current circuit breaker.
Practical example: Carpentry shop
The result
Production interruption, loss of time, and financial damage.
If RCDs trip without any apparent fault, the cause is often operational leakage currents. A differential current measurement during operation shows how heavily the RCD is actually loaded and whether limit values are being exceeded.
Read this article to find out how this measurement works and what insights it provides.