3 Fragen 3 Antworten mit Optec

3 questions - 3 answers

With Peter Graf
If you want to evaluate RCD tripping, you need more than just a simple current measurement. Only differential current measurement shows how heavily a residual current device is actually loaded and why it trips.

Why is a measurement with the current clamp not sufficient?


A true RMS current clamp only measures the differential current flowing to ground. It does not show which circuits this current originates from, nor which frequency components are contained.

Frequency-controlled drives in particular generate high-frequency leakage currents in addition to low-frequency currents. These have a significant influence on the tripping behavior of the RCD. A true RMS clamp meter measurement therefore cannot be used to assess how close the RCD is already operating to its tripping value. The actual cause of the shutdown remains hidden.

What does a residual current measurement show?

The differential current measurement records the sum of all currents in the forward and return conductors. In a fault-free state, this sum is almost zero. In addition, the frequency components can be analyzed. This reveals the proportion caused by operational leakage currents and whether these occur permanently or only briefly. The measurement shows how much of the rated residual current of the RCD has already been utilized. This makes it clear whether the tripping can be explained by operation or indicates a fault.

What are the benefits for the company?

Residual current measurement creates transparency during operation. It shows whether normative limit values are being complied with and whether the RCD is still operating reliably.


On this basis, targeted measures can be planned, such as the division of electrical circuits, the use of suitable filters to reduce operating-related leakage currents, or the adaptation of EMC measures. Decisions are no longer made on gut feeling, but on the basis of measurement data.

Back to the practical example of carpentry

Peter Graf
In the case of the CNC system, the differential current measurement shows that the unwanted tripping of the RCD is not caused by a defect. Rather, it becomes apparent that the sum of the operating-related leakage currents exceeds the tripping value of the RCD during certain work steps.

This explains why the CNC system shuts down even though the insulation is OK and why the problem occurs repeatedly. Only this insight enables a solution that stabilizes operation and prevents further production interruptions.
Peter Graf

Thank you very much, Peter, for the technical explanation.

We would be happy to show you how to monitor residual currents in your system in a targeted manner. Please

contact us.

The Optec team answers