B.92057204

ATiCS2CH-63A-ISO 400V

Automatisches Umschalt- und Überwachungsgerät Schweizer Standardausführung gemäss NIN Kap.7.10 (ergänzend zu Kap.1-6) & EN 61439

Switching and IT system monitoring in a single device

For Group 2 medical applications

Functional safety SIL 2, TÜV SÜD-certified

Uninterrupted testing thanks to the bypass option

The ATICS®-…-ISO series of switching and monitoring devices includes all the functions needed to switch between two independent power lines and to monitor ungrounded power supplies. The integration of the power section and the electronics into a flat, compact device reduces the space required in the control cabinet, minimizes wiring effort, and reduces the potential for errors. To ensure maximum reliability, ATICS® was developed in strict accordance with functional safety guidelines (SIL 2).

Connectors on all input lines—in combination with the optional bypass switch—enable uninterrupted testing of the ATICS®. In the event of service, this allows for replacement without interrupting power. ATICS® thus enhances the level of safety, particularly in intensive care units and operating rooms.


Applications Use in sensitive systems, such as those in Group 2 medical areas, which require a safe and reliable power supply even in the event of malfunctions. Redundant power cables and the design of the power distribution network as an (ungrounded) IT system make a significant contribution to ensuring a safe power supply.

Features and Functions:


· Perfect for space-saving installation / retrofit

· Compact unit for the easy setup of safety power supplies with functional safety in accordance with DIN EN 61508 (SIL 2), e.g., for medical areas of Group 2 according to DIN VDE 0100-710 (VDE 0100-710) / IEC 60364-7-710

· Enhanced safety and availability through the integration of switching and IT system monitoring in a single compact unit

· All-in-one: Integration of load break switch and control

· Solutions for every application

· Convenient installation and commissioning

· For sensitive systems in Group 2 medical environments

· Insulation monitoring included in the scope of functionality

· Saves time and money

· Safe in operation

· Robust load-break switch contacts

· Mechanical interlock

· Manual operation directly on the device

· Functional safety SIL 2

· Certified by TÜV SÜD in accordance with EN 61508 (VDE 0803) SIL 2 and DIN VDE 0100-710 (VDE 0100-710)

· Uninterrupted maintenance

·

· Plug-in connections and optional bypass switch

· Excellent communication and parameterization capabilities


Technical Specifications:


· Overvoltage category: III

· Special firmware suitable for Swiss applications

· Rated operating voltage Ue: 230 V (AC 160–276 V)

· Supply voltage Us: from a monitored power grid

· Communication via RS485 / BMS bus for native integration into existing BMS bus structures

· Mains voltage Un (operating range): 400 V AC

· Frequency range fn: 48...62 Hz

· Insulation monitoring: Measurement range: 10 kΩ…1 MΩ

· Threshold value Ran1 (ALARM 1): 50…500 kΩ

· Load current monitoring (IT system transformer)

· Measurement range IL (TRMS): 10…110% of the trip threshold

· Adjustable threshold: 5…(50) 100 A (in 1 A increments)

· Includes current transformers STW2 and STW3.

· Mains connection monitoring

· PE connection monitoring

· Self-monitoring with automatic notification

· Temperature monitoring (IT system transformer)

· PTC thermistors per DIN 44081, max. 6 in series

· Output: 1 potential-free changeover contact

· Dimensions: W234 x H263 x D73.5 mm

· Functional safety according to SIL 2

· Output short-circuit monitoring


Installation orientation:


As specified in the technical manual: Display-oriented = horizontal