EDS151CH Isoscan Isolationsfehlersuchgerät

zu IsoMED427P-CH oder ATICS-CH...ISO Schweizer Standardausführung gemäss NIN Kap.7.10 (ergänzend zu Kap.1-6) & EN 61439

Insulation fault detection with 6 integrated transducers

Up to 528 outputs can be combined via the BMS bus

Response sensitivity: 0.5 mA

Response time: max. 8 s according to IEC 61557-9

The EDS150/151 insulation fault locator is used, in conjunction with the ISOMETER® IRDH575 or the PGH test current generator, to locate insulation faults in unearthed power supply systems (IT systems). To do this, they use built-in current transformers to detect the test current signals generated by the ISOMETER® IRDH575 or the PGH test current generator and evaluate them accordingly. Each EDS150/151 unit has six built-in current transformers through which all current-carrying conductors of a branch circuit can be routed. The response time for an alarm notification, including a message displayed on a corresponding indicator (e.g., MK2430/MK800), is a maximum of 8 seconds.


A total of up to 88 EDS150/151 units can be connected via an RS485 interface (BMS protocol), allowing for the monitoring of up to 528 circuits. Activity on the BMS bus is indicated by a status LED.

Key Features:


· Automated insulation fault detection during operation

· Application: Control circuits

· 6 measurement channels

· Integrated measurement current transformers

· Universal system concept


Features and Functions:


· Insulation fault detection in AC, AC/DC, and DC IT systems

· 6 measurement channels with current transformers per EDS151

· Up to 528 measurement channels can be combined in the monitored IT system via the BMS bus: 88 x 6 measurement channels

· EDS151 response sensitivity: 0.5 mA

· Maximum response time of 8 s in the AC grid according to IEC 61557-9

· RS-485 interface with BMS protocol

· BMS address range 3…90

· Cyclic self-test


Technical Features:


· For AC, AC/DC, and DC IT power systems

· 6 measurement channels

· Special firmware suitable for Swiss applications

· Up to 88 EDS units can be combined via the BMS bus (528 measurement channels)

· Response sensitivity: 0.5 mA

· Inner diameter: 10 mm

· Dimensions: W 245 x H 26 x D 38 mm

· Weight: 340 g


Applications:


· Insulation fault detection in AC, AC/DC, and DC IT systems

· Main power circuits in industrial plants, power plants, and ships

· IT systems for medical facilities and control circuits


Optional accessory: AN450-CH