Residual current monitoring SmartDetect RCMS
The LINETRAXX SmartDetect RCMS410/RCMS425-L/RCMS425-D is a measuring device for monitoring differential currents in grounded power supply networks. It can monitor 4 measuring channels simultaneously and measures differential currents between 2 mA and 70 A at DC voltage and in a frequency range of 0 Hz to 100 Hz.
power supply networks. It can monitor 4 measuring channels simultaneously and
measures differential currents between 2 mA and 70 A at DC voltage and in
a frequency range from 15 Hz to 20 kHz AC voltage.
Type selection
| Type | Display | IOs Relay | Power supply |
RCMS410 | LED bar graph | M+, Q, I | DC 24 V |
| RCMS425-L | LED bar graph | M+, Q, I; K1, K2 | DC 24 V; AC/DC 100...240 V |
RCMS425-D | TFT display | M+, Q, I; K1, K2 | DC 24 V; AC/DC 100...240 V |
LED bar graph with (RCMS410, RCMS425-L)
- Device status LED
- LEDs for warning and main alarm
- Alarm LEDs per channel
TFT display (RCMS425-D)
- Device status LED
- Alarm LED
- Full-text menu
- 4-button navigation
Function modules: 
- A: Harmonic analysis (FFT)  
- B: All-current-sensitive measurement for use with current transformer series type B/B+
- C: External transformer connection type A
- 4 channels in a compact housing
- Alternating, pulse, and/or all-current sensitive measurement per channel
- Analysis of harmonics up to the 400th harmonic
- Adjustable frequency response
- Communication via various interfaces
- Measuring and evaluating differential, fault, and rated currents of consumers and systems
- Monitoring the differential currents of stationary electrical systems and equipment as an alternative to RIso testingin accordance with accident prevention regulation DGUV V3 and industrial safety regulation BetrSichV
- Detecting gradual deterioration of insulation supports preventive maintenance
- Monitoring of fire-hazardous currents in fire-prone operating facilities
- EMC monitoring of TN-S systems for "stray" currents and additional N-PE bridges
- Monitoring of PE and PA conductors for freedom from current
- Monitoring of N conductors for overload due to harmonics
- Monitoring of digital inputs