Shop
MPW 128 Pegelwandler Ethernet/M-Bus
M-Bus level converter for up to 128 devices
Connection to M-Bus master via 10/100 Ethernet
Galvanic isolation between Ethernet and M-Bus
Mounts on a 35 mm DIN rail
The optec MPW-128-IP M-Bus level converter allows up to 128 M-Bus devices to be connected to an M-Bus master via an Ethernet connection. The M-Bus master can be, for example, a PC or an “embedded controller.” The level converter converts the signals coming from the M-Bus master via the Ethernet interface into M-Bus signals.
Features and Functions:
· M-Bus level converter for up to 128 M-Bus devices (standard load: 1.5 mA)
· 10/100 Mbps Ethernet
· Fixed or dynamic IP address
· Ethernet interface and M-Bus are electrically isolated
· 300 to 9,600 baud M-Bus transmission rate
· Full M-Bus voltage range from 36 V to 42 V
· Bit regeneration
· Echo suppression
· Overcurrent protection
· Overvoltage protection
· 4 parallel M-Bus connections
· Housing compliant with EN 50022 for mounting on DIN rails
Technical Specifications:
· Supply voltage 20 V to 28 V AC/DC
· M-Bus voltage 36 V–42 V
· Max. M-Bus quiescent current: 180 mA (120 standard loads)
· Overcurrent threshold: 200 mA
· Galvanic isolation between Ethernet and M-Bus
· Ethernet 10/100BaseT
· M-Bus baud rate: 300 … 9600 baud
· M-Bus connection: 4 separate terminal pairs, max. 2.5 mm²
· Ethernet connection: Western RJ-45 jack
· Operating temperature: 0 … 55°C
· Relative humidity: 0 … 90% (non-condensing)
· Housing compliant with EN 50022 for mounting on a 35 mm DIN rail,
· Dimensions (L x W x H): 108 x 90 x 66 mm