EPA.50275585

NF-KC-DAR-63-3

Kombinierter EMV- und Ableitstromreduktionsfilter Abmessungen (LxBxH): 450 x 80 x 135 mm

Rated current 63 A, 520 VAC

Prevents false tripping of RCDs

Improved EMC

This EMC filter enhances the operational safety of systems equipped with ground-fault circuit interrupters by effectively suppressing unwanted leakage currents starting at 2 kHz

Rated voltage: 520 VAC, 3-phase

Rated frequency: 50/60 Hz

Rated current: 63 A @ 50°C

Power loss Pv: approx. 23 W

Dimensions (L x W x H): 450 x 80 x 135 mm

Weight: approx. 3.7 kg

Customs tariff number: 85045000

Country of origin: UK

- Reduction of leakage currents in the clock frequency range

- Significant improvement in EMC

- Prevents unintended RCD tripping

- Suitable for frequency converters and servo controllers with long motor cables

Overload capacity: 4 times the rated current at power-up,

then 1.5 times the rated current for 1 minute,

once per hour

Design: Metal housing

Protection rating: IP20

Mounting: Mounting brackets with holes

Connections: Screw terminals 25 mm²,

PE (enclosure grounding via M6 threaded bolt)

Approvals: CE, cURus (E504515)

Manufactured in accordance with: EN 60939, UL 1283, CSA 22.2 No. 8, RoHS

Operation and storage: EN 60721-3-1: 1K3, EN 60721-3-2: 2K3, EN 60721-3-3: 3K3

Flammability rating: UL 94V-2 or better

IEC climate category: 25/85/21 (-25°C to +85°C)