UMG 512-PRO 230V-CH-UL Master Messgerät PQ Top
Class A Power Quality Analyzer
Harmonics up to the 63rd harmonic
Additional residual current monitoring (RCM)
256 MB memory, Jasic PLC functionality
The UMG 512-PRO power quality analyzer (Class A) measures all power quality parameters (e.g., overvoltage up to the 63rd harmonic, flicker, short-term interruptions, etc.) and also serves as a residual current monitor. Unlike the UMG 511, it features a temperature input. The device complies with current standards, such as EN 50160, IEEE 519, and EN 61000-2-4. It also features a 256 MB measurement data memory and can be programmed graphically using Jasic (PLC functionality). Network interfaces and the open communication architecture with numerous protocols (Modbus, IP) enable easy integration into higher-level systems. The UMG 512-PRO has two digital inputs and two digital outputs.
Pre-installed apps:
· Measurement Value Monitor
· EN 50160 Watchdog PRO
· IEC 61000-2-4 Watchdog PRO
· Push Service PRO (optional, not pre-installed)
Key Features:
· Optec Data Logging Kit for Switzerland (CH)
· Measurement Value Monitor: Graphically presented data on the device’s own homepage without the need for additional software installation
· EN 50160 Watchdog PRO: Continuous monitoring of power quality in accordance with EN 50160 in power supply networks
· IEC 61000-2-4 Watchdog PRO: Continuous monitoring of power quality in accordance with IEC 61000-2-4 in customer-side power grids
· Push Service PRO: Automatic transmission of measurement data directly from the meter to a cloud service
· Harmonic analysis up to the 63rd harmonic, even/odd (U, I, P, Q)
· Interharmonics (U, I), distortion factors THD-U / THD-I / TDD
· Measurement of phase, anti-phase, and zero-sequence components, unbalance, rotating field direction, and voltage crest factor
· Flicker measurement according to DIN EN 61000-4-15, acquisition and storage of transients (> 39 µs)
· Short-term interruptions (from 10 ms), display with rms values and waveform
· Continuous true RMS measurement
· Measurement procedures in accordance with IEC 61000-4-30
· Certified measurement accuracy according to Class A
· Continuous sampling of voltage and current inputs at 25,600 Hz
· Measurement accuracy for active energy: Class 0.2
· Measurement of currents and voltages (15–440 Hz)
· Communication: Profibus (DP/V0), Modbus (RTU, TCP, Gateway), TCP/IP, BACnet (optional)
· HTTP, FTP (file transfer), TFTP, NTP (time synchronization), SMTP (email function), DHCP, SNMP
· Interfaces: Ethernet, Profibus / RS485 (DSUB-9)
· Large measurement data memory (256 MB Flash)
· 2 digital inputs, 2 digital outputs, 2 direct reference current inputs, and a temperature measurement input
Communication:
· Profibus (DP/V0)
· Modbus (RTU, TCP, gateway)
· TCP/IP
· BACnet (optional)
· HTTP
· FTP (File Transfer)
· TFTP
· NTP (time synchronization)
· SMTP (email function)
· DHCP
· SNMP
Interfaces:
· Ethernet
· Profibus / RS485 (DSUB-9)
· RS485 Modbus (terminal block)
Measurement accuracy:
· Operating: Class 0.2S (... / 5 A)
· Current: 0.1%
· Voltage: 0.1%
Power Quality:
· Harmonics up to the 63rd harmonic, even/odd
· Flicker measurement
· Short-term interruptions (10 ms and longer)
· Transient recorder (> 39 µs)
· Inrush currents (> 10 ms)
· Unbalance
· Half-wave RMS recordings (up to 11 min.)
· Events can be displayed as waveforms
Networks:
· IT, TN, and TT power systems
· 3- and 4-phase networks
Measurement data storage:
· 256 MB Flash
· 32 MB SDRAM
Programming language:
· Graphical programming
· Jasic programming language
· PLC functionality
2 digital inputs:
· Pulse input
· Logic input
· Status monitoring
· HT/NT switching
2 digital outputs:
· Pulse output (kWh / kvarh)
· Switching output
· Threshold output
· Logic output
· (expandable via external I/O modules)
RCM - Residual Current Monitoring:
· 2 differential current inputs
Temperature measurement input:
· PT100, PT1000, KTY83, KTY84
Grid visualization software:
· Free GridVis Essentials
Installation:
· 3-phase, 3- and 4-wire connection
· Voltage 3x400/230V
· Current transformer setting: ..../5 A
· Supply voltage: 95–240 VAC / 80–300 VDC
· Dimensions: W 144 x H 144 x D 45 mm