High-precision universal measuring device
J.52.34.002

UMG 96-S2-CH RS485 Modbus Messgerät

Slave Gerät mit RS485, Modbus RTU

Universal energy meter for TN and TT systems

Active energy with accuracy class 0.5S

Open communication via Modbus RTU (RS485)

Compact 96-series design with shallow mounting depth

The new UMG 96-S2 energy meter stands out as a versatile, all-purpose device. It is suitable for measuring and monitoring electrical parameters and energy consumption, as well as for monitoring power quality parameters such as harmonics. Applications include energy distribution systems, for example, for cost center tracking and threshold monitoring. Furthermore, the device can be used as a data transmitter for building automation systems or a PLC.

Key Features:


· Suitable for TN and TT systems with 1 and 5 A transformer connections

· Active energy with accuracy class 0.5S (... / 5 A transformer)

· Easy tariff switching as an additional component for energy and cost transparency

· Easy integration into higher-level systems

· Open communication channel via Modbus RTU

· Easy to use with minimal configuration effort

· High performance in a compact 96-series design with a shallow mounting depth

· Extensive options for data processing

· Multifunction meter with an easy-to-read LCD display


General


· Measurement accuracy for voltage and current: 0.2%

· Measurement accuracy for active energy (kWh, ... / 5 A): Class 0.5S


Inputs and Outputs


· Digital output: 1

· Pulse output


RMS measurement—instantaneous values, e.g.:


· Current, voltage, frequency

· Active, reactive, and apparent power

· Power factor


Measurement of average values, e.g.:


· Voltage, current / current and maximum

· Active, reactive, and apparent power / current and maximum

· Frequency / current and maximum


Voltage quality measurement


· Harmonics by order / current and voltage: 1st–15th

· Total harmonic distortion (THD-U / THD-I) in %


Interface / Protocol


· RS485 / Modbus RTU


Environmental Conditions


· Temperature range, operation: K55 (-10... +55 °C)


Measurement current input (3 each)


· Rated current: 1 / 5 A

· Overvoltage category: 300 V CAT II

· Sampling frequency: 8 kHz


Energy measurement


· Active, reactive, and apparent power

· Tariff switching


Measurement voltage inputs (4 each)


· Overvoltage category: 300 V CAT III

· Measurement range, voltage L-N, AC (without transformer): 0 ... 300 Vrms

· Measurement range, voltage L-L AC (without transformer): 0 ... 425 Vrms

· Frequency measurement range: 45 ... 65 Hz

· Sampling frequency per channel (50/60 Hz): 8 kHz

· Measurement in quadrants: 4

· Systems: TN, TT


Grid visualization software


· Free GridVis Essentials


Installation:


· Connection: Voltage 3x230/400V

· 3-phase, 4-wire connection, 50/60 Hz

· Current: .../5 A, with galvanic isolation,

· Dimensions WxHxD: 96x9648 mm

· Protection class according to EN 60529 (with gasket = IP54): Front IP40 / Rear IP20

· Installation per IEC EN 60999-1/DIN EN 50022: Panel mounting