UMG 96RM-PN-CH mit 90...277 V AC, 90...250 V DC
PROFINET-certified according to IEC 61158
Integrated residual current monitoring (RCM)
Integrated web server with real-time measurement values
REST interface for building management systems, PLCs, and SCADA
The UMG 96RM-PN is PROFINET-certified and suitable for use with PROFIenergy. A PROFINET certificate attests to compliance with IEC 61158 standards within a PROFINET network, thereby ensuring a high standard of quality. The UMG 96RM-PN not only enables continuous consumption monitoring but also residual current monitoring (RCM). RCM allows for the detection of faults that a single system would only partially detect or fail to detect altogether. The integrated web server can display current power, current, and voltage values in real time via the device’s homepage. The REST interface for retrieving measurement values via the HTTP protocol, e.g., for integrating the measurement data into higher-level software solutions (GLT, PLC, SCADA, etc.)
Key Features:
· PROFINET-compliant Ethernet interfaces and internal switch for setting up line topologies
· Multifunction meter with easy-to-read LCD display
· RS485 interface with Modbus/RTU protocol
· 2 digital outputs (pulse output, switching output, limit output, logic output)
· Optional 3 digital inputs or outputs
· Optional 2 RCM or temperature inputs
· Detailed recording of energy data and load profile
· Energy management systems (ISO 50001)
· High sampling rate of 21.3 kHz
· Harmonic analyzer up to the 40th harmonic
· Plug-in screw terminals
· Backlight
· Calculation of energy costs
· Power quality monitoring
· Meter with an accuracy of 0.2% (V), kWh class = 0.5S
· Energy meter with 8 rates, active and reactive energy
Communication:
· PROFINET
· PROFIenergy
· TCP/IP
· Modbus/TCP
· Modbus/RTU (RS485)
· HTTP/REST
Interfaces:
· RS485
· Ethernet
· PROFINET
Measurement accuracy:
· Active energy: Class 0.5S (kWh, …/5 A)
· Current: 0.2%
· Voltage: 0.2%
Voltage quality:
· Harmonics up to the 40th harmonic
· Rotating-field components
· Total Harmonic Distortion (THD-U / THD-I)
Power systems:
· TN, TT, and IT power systems
· 3- and 4-phase power systems
· Up to 4 single-phase power systems
Temperature measurement input:
· PT100, PT1000, KTY83, KTY84
2 digital outputs:
· Pulse output (kWh / kvarh)
· Switching output
· Threshold output
· Logic output
· Remote via Modbus / Profibus
3 digital inputs/outputs:
· Can be configured as inputs or outputs
2 analog inputs:
· Analog, temperature, or differential current input (RCM)
Grid visualization software:
· Free GridVis Essentials
Installation:
· Supply voltage: 90–277 V AC (45–65 Hz)
· Current Transformer: .../5 A with 3- and/or 4-wire measurement in the neutral conductor
· Dimensions: W 96 x H 96 x D 74 mm