Modbus / Ethernet / 24V
J.52.22.063

UMG 96RM-E-CH mit 24...90 V AC, 24...90 V DC

Master Gerät mit Ethernet TCP/IP und Web Browser

Energy meter with Ethernet and RCM

Residual current monitoring with a 5 mA trip current

256 MB data storage with clock

Modbus RTU/TCP, HTTP, SNMP, FTP

The innovative UMG 96 RM-E energy meter monitors and measures residual currents (RCM – Residual Current Monitor) as well as currents at the central grounding point (ZEP). The UMG 96 RM-E multifunctional power analyzer can be used to monitor and control electrical parameters in power distribution systems or for continuous monitoring of residual currents.

Key Features:


· Optec Data Logging Kit (Switzerland)

· Multifunction meter with easy-to-read LCD display

· UMG 96RM-E energy meter with Ethernet and RCM

· (UL) Supply voltage 90 V–277 V (50/60 Hz); 90 V–250 V DC

· 300 V CAT III voltage measurement

· Measurement category: 300 V CAT III

· 3 voltage measurement inputs (L-N: 20 V–300 V; L-L: 34 V–520 V; 45 Hz–65 Hz)

· 3+1 current measurement inputs 0–5 A

· Response current: 5 mA

· Measurement in three-phase, 4-wire systems with a grounded neutral conductor up to 277 V / 480 V

· Measurement in ungrounded three-phase, three-wire systems up to 480 V

· Measurement in single-phase 3-wire systems up to max. 220 V–440 V

· Measurement in single-phase 2-wire systems up to 220 V

· 2 digital outputs; 3 digital inputs/outputs, configurable

· 2 analog inputs, optionally also as temperature or residual current measurement inputs (RCM)

· Clock and data memory (256 MB flash)

· Interfaces: Ethernet, RS485

· Protocol: TCP/IP, Modbus RTU


Communication:


· Modbus (RTU, TCP, gateway)

· TCP/IP

· HTTP (freely configurable homepage)

· FTP (file transfer)

· SNMP

· NTP (time synchronization)

· SMTP (email function)

· DHCP

· SNTP

· TFTP

· BACnet (optional)


Interfaces:


· RS485

· Ethernet


Measurement accuracy:


· Operating: Class 0.5 (... / 5 A)

· Current: 0.2%

· Voltage: 0.2%


Voltage quality:


· Harmonics up to the 40th harmonic

· Rotating-field components

· Distortion factor THD-U / THD-I


Power systems:


· TN, TT, and IT power systems

· 3- and 4-phase power systems

· Up to 4 single-phase power systems


Measurement data storage:


· 256 MB flash


Temperature measurement inputs:


· PT100, PT1000, KTY83, KTY84


2 digital outputs:


· Pulse output (kWh / kvarh)

· Switching output

· Threshold output

· Logic output

· Remote via Modbus / Profibus


3 digital inputs/outputs:


· Optional inputs or outputs


2 analog inputs:


· Analog, temperature, or differential current input (RCM)


Grid visualization software:


· Free GridVis Essentials


Installation:


· Supply voltage: 24...90 V AC, 24...90 V DC (45...65 Hz)

· Current transformer: .../5 A with 3- or 4-wire measurement

· TCP/IP interface for network connection

· (External sensors are not included in the price of the device)

· Dimensions: W 96 x H 96 x D 74 mm