Modbus / USB / 230V
J.52.22.066

UMG 96RM-CBM-CH mit 90...277 V AC, 90...250 V DC

Slave Hauptgerät mit Speicher und Uhr, RS485

Universal measuring device with RS485, USB, and backup battery

Large, freely configurable measurement data memory

Harmonic analysis up to the 40th harmonic

Accuracy: 0.2%, kWh Class 0.5S

The UMG 96RM-CBM, featuring a large measurement data memory, RS485 (Modbus RTU), a USB interface, and a battery, is a highly compact and powerful universal measuring instrument designed primarily for use in low- and medium-voltage distribution systems. In addition to measuring a wide range of electrical parameters, this innovative meter offers a variety of additional functions, such as the measurement of harmonics up to the 40th order. Continuous sampling at 21.3 or 25.6 kHz enables high-resolution data acquisition, making it an effective tool for energy management, fault analysis, and power quality monitoring.

· Key Features:

·

· Optec Data Logger Kit (Switzerland)

· Multifunction measuring device with easy-to-read LCD display

· Large measurement data memory; recording is freely configurable

· USB interface

· Built-in backup battery

· RS485 interface with Modbus protocol and 2 digital outputs (as switch or pulse outputs)

· Detailed recording of energy data and load profiles

· Energy management systems (ISO 50001)

· Large measurement data memory

· High sampling rate of 21.3 kHz

· Harmonic analyzer up to the 40th harmonic

· Plug-in screw terminals

· Backlight

· Energy cost calculation

· Power quality monitoring

· Meter with an accuracy of 0.2% (V), kWh class = 0.5S

· Energy meter with 8 rates, active and reactive energy


Communication:


· Modbus (RTU)

· Profibus DP V0 (optional)

· TCP/IP (optional)

· M-Bus (optional)


Interfaces:


· RS485

· USB


Measurement accuracy:


· Operating: Class 0.5 (... / 5 A)

· Current: 0.2%

· Voltage: 0.2%


Power Quality:


· Harmonics up to the 40th harmonic

· Rotating-field components

· Total Harmonic Distortion (THD-U / THD-I)


Power systems:


· TN, TT, and IT power systems

· 3- and 4-phase power systems

· Up to 4 single-phase power systems


Measurement Data Storage (UMG 96RM-CBM, UMG 96RM-P):


(UMG 96RM, UMG 96RM-M, and UMG 96RM-EL do not have measurement data storage; operating, minimum,

and maximum values are stored in EEPROM)

· 256 MB Flash


Up to 6 digital outputs:


· Pulse output kWh / kvarh

· Switching output

· Threshold output

· Logic output

· Remote via Modbus / Profibus


3 digital inputs/outputs:


· Selectable as inputs or outputs


Grid visualization software:


· Free GridVis Essentials


Installation:


· Supply voltage: 90–277 V AC (45–65 Hz)

· Current transformer: .../5 A with 3- or 4-wire measurement

· USB interface; USB cable included

· Dimensions: W 96 x H 96 x D 74 mm