This range complements selected articles
Low-Power-Stromwandler bieten zahlreiche Vorteile gegenüber konventionellen Wandlern. Sie müssen z.B. während der Installation oder Servicearbeiten nicht kurzgeschlossen werden, wodurch die Wandlertrennklemmen entfallen. Dadurch sparen Sie im Schaltschrank eine Menge Platz und die Kosten für die Trennklemmen sowie deren Installation.
Diese Low-Power Stromwandler sind kompatibel mit:
· Erweiterungsmodul 800-CT8-LP in Kombination mit dem UMG 801
· Netzanalysator UMG 96-PQ-L-LP
UMG 96-PQ-L-LP-CH 90...277 V AC, 90...250 V DC
Product description
The power quality analyzer scores with a large memory that offers up to 15 years of storage space thanks to special data compression. Expandable with plug-in module for Ethernet connection. Temperature monitoring via optional sensor and RCM residual current monitoring.
Low-power inputs
- Switchable current measurement channel
- Low-power current measurement channel for cost-effective 333 mV current transformers
- Current measurement with passive Rogowski coils e.g. 100 mV/1 kA
Voltage quality:
- Harmonics up to the 65th harmonic
- 13.67 kHz sampling frequency
Peripherals:
- 3 digital outputs
- 1 analog output
- 2 digital inputs
Communication:
- Slave/gateway function
- Ethernet interface (optional)
- RS485
Memory:
- High memory depth with low memory requirement
- Memory depth up to 15 years with 10 measured values per quarter of an hour
- Memory partitioning into long-term memory and high-resolution short-term memory
Operation:
- 6-button operation on the color graphic display
- Intuitive operation
- Configuration directly on the display
- On-site operation
- Adjustable home screen and return screen
Visualization:
- Oscilloscope function
- Pointer diagram on the display
- Trailing pointer history on the display
Installation and integration:
- Overvoltage category 600 V CAT III
- Easy installation thanks to 96 x 96 mm front panel
- EMC class B
Energy management:
- Identification of potential savings
- Class 0.2S
- Compliance with regulatory & tax requirements
Modularity:
- Record temperature and monitor via integrated comparator
- Ethernet interface and Modbus gateway
- Residual current measurement or DC power measurement
- Neutral conductor measurement (I4 - current measurement)
Technical features:
- Supply voltage 90...277 VAC, 90...250 VDC
- 3x digital input/output each
- 1x analog output
- 64 MB measurement data memory
- 65th harmonic
- Clock and battery
- RS485 - Modbus
- UL certified
- Dimensions 96x96x86 mm
Application note:
- The UMG 96-PQ-L-LP can only be operated with the optional low-power or Rogowski converter.
- IEC 61000-4-30 Class S from GridVis 9.1.40 optional with article number J.52.36.020