J.14.02.042

UMG 806-LP Modulares Universalmessgerät

inklusive Netzvisualisierungssoftware GridVis-Essential

Measurement inputs for low-power converters: 333 mV

No need to short-circuit the secondary side of the converter

Differential current measurement and temperature input

Onboard Modbus-RTU; TCP and SNMP via module

The UMG 806-LP features measurement inputs for connecting low-power transducers. These transducers are characterized by a very low secondary-side output voltage. Due to the small signal on the transducer line, the secondary side of the transducer does not need to be short-circuited during open-circuit operation. This increases safety during installation and significantly simplifies the installation process. In addition, low-power transformers offer cost advantages over many conventional transformer models, making them a cost-effective alternative.

Functions and Features:


· 4 low-power converters with 333 mV

· Differential current measurement

· Temperature input

· Pulse output

· Onboard Modbus-RTU

· Modbus-TCP – via module

· SNMP V2c – via module


Power Quality Measurement:


· Harmonics up to the 31st harmonic

· Internal 4 MB data memory


Technical Specifications:


· Rated voltage 100...300 V AC/DC

· Power consumption: max. 7 VA

· Backlit display

· 90 mm × 90 mm × 63.5 mm

· Protection class IP20


Voltage measurement:


· 230 VLN / 400 VLL (+/-10%) per IEC

· 400 VL-L (+/-10%) per IEC

· Sampling frequency 8 kHz / phase


Current measurement (333 mV)


· RCM rated current 40 mA

· 4 channels

· Measurement range 0.005 to 6 Arms


Interface:


· RS485 interface (2-wire)

· Modbus-RTU protocol

· Transmission rate up to 38.4 kbps


Functional Note:


Compatible with the EI1 module for the RCM 202-AB, for retrofitting Type A and Type B measurements


Application Note:


Ideal for DIN rail mounting in data centers and industrial settings

Fully integrated into Gridvis