J.52.16.229-PRO

UMG 605 E-PRO 24V-CH-UL Master Messgerät nach EN50160

PQ Messgerät mit Schnittstelle TCP-IP, Uhr und Speicher mit vorinstallierten App's: Messwertmonitor, EN 50160 Watchdog IEC 61000-2-4 Watchdog, (Push Dienst optional)

DIN-rail-mounted power quality analyzer

EN 50160 and IEC 61000-2-4 Watchdog PRO

Harmonic analysis up to the 63rd harmonic

Transient measurement starting at 50 µs

The UMG 604-PRO power quality analyzer is more than just a multifunction meter. It can be used as a transient recorder, meter (kWh, kvarh), harmonic analyzer, PLC, condition monitor, event logger, and data logger. The UMG 604-PRO can be considered the counterpart to front-panel devices in a slim, cost-optimized DIN-rail format. It also offers multiple interfaces with numerous protocols (Modbus, IP, SNMP, NTP, HTTP, BACnet, etc.), as well as a temperature measurement input. The 128 MB measurement data memory ensures redundant and secure data recording.

Key Features:


· Measurement Value Monitor: Graphically presented data on the device’s own homepage without the need to install additional software

· EN 50160 Watchdog PRO: Continuous monitoring of power quality in accordance with EN 50160 in power supply networks

· IEC 61000-2-4 Watchdog PRO: Continuous monitoring of power quality in accordance with IEC 61000-2-4 in customer-side power grids

· Push Service PRO: Automatic transmission of measurement data directly from the meter to a cloud service

· Acquisition and storage of transients (> 50 µs)

· Continuous voltage quality monitoring (e.g., EN 50160)

· Harmonic analysis up to the 63rd harmonic, even/odd

· Interharmonics, total harmonic distortion (THD-U / THD-I), measurement of phase, zero-sequence, and neutral sequences

· Flicker measurement in accordance with DIN EN 61000-4-15

· Acquisition and storage of transients (> 50 µs)

· Recording of short-term interruptions (from 20 ms)

· Monitoring startup processes

· Recorder for limit value events

· Acquisition and digitization of true RMS values for currents and voltages (15–440 Hz)

· Recording of more than 2,000 measured values per measurement cycle (200 ms) /li>

· Automatic generation and transmission of power quality reports

· Modern communication architecture via Ethernet

· Fast and reliable data transmission via RS485 interface, up to 921.6 kB/s

· User-friendly web interface and email functions

· Communication: Profibus (DP/V0), Modbus (RTU, TCP, Gateway), TCP/IP, BACnet (optional)

· HTTP, FTP (file transfer), TFTP, NTP (time synchronization), SMTP (email function), DHCP, SNMP

· Interfaces: Ethernet, RS-485 (Modbus and Profibus), RS-232

· 2 digital inputs and 2 digital outputs



Communication


· Profibus (DP/V0)

· Modbus (RTU, TCP, gateway)

· TCP/IP

· BACnet (optional)

· HTTP (freely configurable homepage)

· FTP (file transfer)

· TFTP (automatic configuration)

· NTP (time synchronization)

· SMTP (email function)

· DHCP

· SNMP


Interfaces


· Ethernet

· RS232

· RS485 (Modbus and Profibus)


Measurement Accuracy


· Operating: Class 0.5S (... / 5 A)

· Current: 0.2%

· Voltage: 0.2%


Peak Load Optimization (optional)


· Up to 64 cut-off levels


Power Quality


· Harmonics up to the 63rd harmonic, even/odd

· Flicker measurement

· Short-term interruptions (20 ms and longer)

· Transient recorder (>50 µs)

· Inrush currents

· Unbalance

· Half-wave RMS recordings (up to 4.5 min.)


Power Systems


· IT, TN, and TT power systems

· 3- and 4-phase power systems

· Up to 4 single-phase networks


Measurement Data Storage


· 128 MB Flash


Programming language


· Jasic


2 digital inputs


· Pulse input

· Logic input *

· Status monitoring *

· HT/NT switching

· Emax reset


2 digital outputs


· Pulse output (kWh / kvarh)

· Switching output *

· Threshold output *

· Emax output *

· Logic output *


*(expandable via external I/O modules)


Temperature measurement input


· PT100, PT1000, KTY83, KTY84


Grid visualization software


· Free GridVis Essentials


Installation:


· 3-phase, 3- and 4-wire connection

· Voltage: 3 x 400/230 V

· Current transformer programming: .../5 A,

· Integrated web server for displaying measured values

· Recording and analysis compliant with EN 50160

· Interfaces: Ethernet 100Base-T,

· Master–slave with RS485; RS232

· Dimensions for DIN rail: W 107.5 x H 82 x D 90 mm

· Auxiliary voltage: 20–55 V AC / 20–77 V DC