Functionally expandable network analyzer
J.52.16.222-PRO

UMG 604 PRO 24V-CH-UL Master Messgerät

Schnittstelle TCP-IP mit Langzeitspeicher und Uhr mit vorinstallierten App's: Messwertmonitor IEC 61000-2-4 Watchdog light, (Push Dienst optional)

DIN-rail-mounted power quality analyzer

IEC 61000-2-4 Watchdog PRO light preinstalled

Transient detection starting at 50 µs

Ethernet, RS485 Modbus, and RS232

The UMG 604-PRO power quality analyzer is more than just a multifunction meter. It can be used as a transient recorder, meter (kWh, kvarh), harmonic analyzer, PLC, condition monitor, event logger, and data logger. The UMG 604-PRO can be considered the counterpart to front-panel devices in a slim, cost-optimized DIN-rail format. It also offers multiple interfaces with numerous protocols (Modbus, IP, SNMP, NTP, HTTP, BACnet, etc.), as well as a temperature measurement input. The 128 MB measurement data memory ensures redundant and secure data recording.

Key Features and Functions:


· Measurement Value Monitor: Graphically presented data on the device’s own homepage without the need to install additional software

· IEC 61000-2-4 Watchdog PRO light: Continuous monitoring of power quality in accordance with the IEC 61000-2-4 standard in customer power grids

· Push Service PRO: Automatic transmission of measurement data directly from the meter to a cloud service

· Mounting on a 35-mm top-hat rail (6TE)

· Harmonic analysis up to the 40th harmonic

· THD-U / THD-I, measurement of phase, neutral, and ground systems

· Short-duration interruptions (20 ms and longer)

· Acquisition and storage of transients (> 50 µs)

· Recording of short-term interruptions (starting at 20 ms)

· Monitoring of startup processes, fault recorder function, rotating field display

· Full-wave RMS recordings (up to 4.5 min.)

· Interfaces: Ethernet, RS485 (Modbus), RS232

· Fast and reliable data transmission via RS485 interface, up to 921.6 kB/s

· User-friendly website and email functions

· Communication: Modbus (RTU, TCP, Gateway), TCP/IP, BACnet (optional), Profibus (DP/V0) (optional), HTTP, FTP (file transfer), TFTP, NTP (time synchronization), SMTP (email function), DHCP, SNMP

· 2 digital inputs, 2 digital outputs, and 1 temperature measurement input


Communication:


· Modbus (RTU, TCP, gateway)

· TCP/IP

· BACnet (optional)

· HTTP (freely configurable homepage)

· FTP (file transfer)

· SNMP

· TFTP (automatic configuration)

· NTP (time synchronization)

· SMTP (email function)

· DHCP


Interfaces


· Ethernet

· RS232

· RS485


Measurement Accuracy


· Operating: Class 0.5 (... / 5 A)

· Current: 0.2%

· Voltage: 0.2%


Peak Load Optimization (optional)


· Up to 64 cut-off levels


Power Quality


· Harmonics up to the 40th harmonic

· Short-duration interruptions (20 ms and longer)

· Transient recorder (> 50 µs)

· Inrush currents (> 20 ms)

· Unbalance

· Full-wave RMS recordings (up to 4.5 min.)


Power Systems


· IT, TN, and TT power systems

· 3- and 4-phase power systems

· Up to 4 single-phase networks


Measurement Data Storage


· 128 MB Flash


Programming language


· Jasic


2 digital inputs


· Pulse input

· Logic input *

· Status monitoring *

· HT/NT switching

· Emax reset


2 digital outputs


· Pulse output (kWh / kvarh)

· Switching output *

· Threshold output *

· Emax output *

· Logic output *


(* Expandable via external I/O modules; see catalog, Chapter 05: Industrial Data Communication)


Temperature measurement input:


· PT100, PT1000, KTY83, KTY84


Grid visualization software


· Free GridVis Essentials


Installation:


· Auxiliary voltage: 20–50 V AC / 20–70 V DC

· Dimensions for DIN rail: W 107.5 x H 82 x D 90 mm