Installation tester 1kV, CAT IV 600V
HT.NEPTUNE

Professionelles TRMS AC-DC Sicherheits-Multimeter

Messkategorie CAT IV 600V / CAT III 1000V ENo. 980236609

1 kV installation tester with multimeter function

Insulation testing from 50 to 1000 V DC in accordance with VDE 0413

Low-resistance measurement with over 200 mA

TRMS voltage measurement up to 1,000 V, CAT IV 600 V

1 kV Installation Tester, CAT IV 600 V with Multimeter Function & Low-Resistance Measurement


Multifunction multimeter for testing electrical installations. Insulation testing at 50, 100, 250, 500, 1000 VDC. (VDE 0413 Part 2) Low-resistance measurement with >200 mA. (VDE 0413 Part 4) Rotating field direction measurement by simply touching the conductors. (VDE 0413 Part 7) Voltage measurement with low input impedance (LoZ). Resistance and continuity testing with buzzer. Voltage: DC, AC TRMS, AC+DC TRMS up to 1000V. Frequency of voltage and/or current.

Features:


· Multifunction multimeter for testing electrical installations

· Insulation testing at 50, 100, 250, 500, 1000 VDC. (VDE 0413 Part 2)

· Low-resistance measurement with >200 mA. (VDE 0413 Part 4)

· Rotating field direction measurement by simply touching the conductors

· Voltage measurement with low input impedance (LoZ).

· Resistance and continuity testing with buzzer.

· Voltage: DC, AC TRMS, AC+DC TRMS up to 1000 V

· Frequency of voltage and/or current

· MAX/MIN/PEAK/HOLD functions

· Precise display with 10,000 points

· Auto-range measurements with automatic AC/DC detection

· Determination of the polarization index (PI) and dielectric absorption ratio (DAR)

· DC, AC TRMS, AC+DC TRMS current up to 3,000 A using an external current transformer

· Leakage current with optional current transformer (HT96U)

· Inrush currents of electric motors (Dynamic Inrush Current)

· Harmonics of current and voltage & THD (%) total harmonic distortion


Technical Features:


· Display: 4-digit LCD, 9999 counts, bar graph, and

· Backlight, polarity indicator

· Measurement method: TRMS

· Power supply: 4 x 1.5 V AAA batteries

· Auto Power OFF: after 15 minutes of inactivity

· Standards: VDE 0413 Parts 2, 4, and 7 (EN 61557-2, -4, and -7)

· Safety: IEC/EN 61010-1, IEC/EN 61010-2-030,

· IEC/EN 61010-2-033 EMC: IEC/EN 61326-1

· Protection class: IP40

· Overvoltage category: CAT IV 600 V, CAT III 1000 V

· Dimensions (L x W x H): 175 x 85 x 55 mm

· Weight (with batteries): 420 g


· ENo. 980 236 609

Neptune, including a pair of alligator clips, red, black

Test leads with Pr1