FAQ: How to properly secure your data center
What standards apply in data centers?
EN 50600 is the central standard for the construction and operation of data centers. It contains specific requirements for:
-
Construction and infrastructure
-
Power supply and air conditioning
-
Security and communication systems
The following also apply to the evaluation of network quality:
-
EN 50160 – for public utility networks
-
EN 61000-2-4 Class 1 – for industrial power supply
These standards form the basis for standard-compliant and safe planning.
What are granularity levels?
In order to use energy efficiently, consumption must be measured accurately. The EN 50600-2-2 standard defines three levels of granularity:
-
Level 1: Total consumption of the data center
-
Level 2: Consumption of individual systems and equipment
-
Level 3: Detailed data for each individual piece of equipment
With each higher level, accuracy increases – as does the potential for optimization.
Reliably detecting fault currents: RCM in the data center
RCM stands for Residual Current Monitoring – the continuous monitoring of fault currents. The aim is to report faults rather than shut down the system.
An RCM system offers the following advantages:
-
Early detection of dangerous fault currents
-
Higher system availability
-
Prevention of fires and EMC problems
-
Reduced testing effort for stationary systems
-
No shutdown required for insulation measurements
Why does the neutral conductor need to be monitored?
In modern data centers, nonlinear loads such as servers or poor-quality power supplies place a heavy strain on the grid. These generate electrical harmonics, particularly third harmonics.
These harmonics add up in the neutral conductor. As a result, the neutral conductor current can be significantly higher than the currents in the individual outer conductors.
If this effect is underestimated, there is a risk of overload – with fatal consequences:
-
Failure of the neutral conductor
-
Voltage shifts in the system
-
Damage to IT systems and infrastructure
With targeted measurement of the neutral conductor, you can identify these risks at an early stage and avoid expensive downtime.
What you should bear in mind when planning
A well-thought-out electrical safety concept is worthwhile. Pay attention to:
Clear definition of measurement points
Documented limit values
Two independent reporting channels (e.g., on site + control room)
Training of personnel in the event of a fault
Regular testing of the alarm systems
Approval by a competent body
This ensures that your system responds correctly in the event of a fault – without failure.