Current transformer RX

  • Standards: IEC/EN 60044-1, BS 3938
  • Accuracy classes: 0.5% or 1%
  • Housing: 10% glass-filled polycarbonate
  • Flame-retardant per UL Standard 94V-0
  • 2 secondary terminals on each side
  • M4 self-locking screws
  • Insulation class: E (120° C maximum)
  • System voltage: 720 V maximum
  • Test voltage: 4 kV at 50 Hz for 1 min.
  • Frequency range: 50 to 60 Hz
  • Primary current ratings: 50 A to 3000 A
  • Secondary current ranges: .../5 A
  • Operating temperature: -20° C to +45° C
  • Storage temperature: -50° C to +80° C
  • Short-term current rating: 60 x I TH
  • Long-term current rating: 2.5 x I TH

Measuring high primary currents; the transformer has a low-current secondary output that can then be connected to measuring instruments, such as the UMG 96.


If the measuring instrument needs to be replaced, the load does not need to be shut off, since the measuring instrument is not directly connected to the supply line. This prevents unplanned downtime of the system.


Important: Operate the current transformer within the upper third of the specified current range.


Installation Note: Observe the current flow direction: P1 in, P2 out

Filter
Primary current
Performance
Accuracy class
Cable opening diameter
Copper rail Dimension max
Primary current
Performance
Accuracy class
Cable opening diameter
Copper rail Dimension max

Filter

Primary current
Performance
Accuracy class
Cable opening diameter
Copper rail Dimension max
Reset filter

Current transformer RX

  • Standards: IEC/EN 60044-1, BS 3938
  • Accuracy classes: 0.5% or 1%
  • Housing: 10% glass-filled polycarbonate
  • Flame-retardant per UL Standard 94V-0
  • 2 secondary terminals on each side
  • M4 self-locking screws
  • Insulation class: E (120° C maximum)
  • System voltage: 720 V maximum
  • Test voltage: 4 kV at 50 Hz for 1 min.
  • Frequency range: 50 to 60 Hz
  • Primary current ratings: 50 A to 3000 A
  • Secondary current ranges: .../5 A
  • Operating temperature: -20° C to +45° C
  • Storage temperature: -50° C to +80° C
  • Short-term current rating: 60 x I TH
  • Long-term current rating: 2.5 x I TH

Measuring high primary currents; the transformer has a low-current secondary output that can then be connected to measuring instruments, such as the UMG 96.


If the measuring instrument needs to be replaced, the load does not need to be shut off, since the measuring instrument is not directly connected to the supply line. This prevents unplanned downtime of the system.


Important: Operate the current transformer within the upper third of the specified current range.


Installation Note: Observe the current flow direction: P1 in, P2 out