B.74043023

RCMA423CH-D-1 Differenzstrom Überwachungsgerät

Allstromsensitiv, für TN und TT Netze Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

All-current-sensitive Type B residual current monitoring

Adjustable trip thresholds from 30 mA to 3 A

Frequency range: 0 to 2000 Hz

Power supply: DC 9.6–94 V / AC 16–72 V

The RCMA423 all-current-sensitive residual current monitor is used to monitor grounded systems (TN and TT systems) in which DC fault currents or residual currents may occur whose magnitude is continuously greater than zero. These include, in particular, loads with six-pulse bridge rectifiers or two-pulse bridge rectifiers with smoothing, such as inverters, chargers, and construction machinery with frequency-controlled drives. Currents in individual conductors can also be monitored with the RCMA423.


The early warning stage (50…100% of the set response value IÄn2) allows a distinction to be made between an early warning and an alarm. Since the measured values are acquired via current transformers, the device is virtually independent of the system’s rated voltage and current.

Features and Functions:


· Type B residual current monitoring device sensitive to all types of current, in accordance with IEC 62020 and IEC 60755

· RMS measurement (AC + DC)

· Two independently adjustable thresholds: 30 mA…3 A

· Frequency range 0…2000 Hz

· Adjustable start-up, response, and reset delays

· Digital measurement display via LCD

· Measurement value memory for trip value

· Connection monitoring for current transformers

· Status LEDs for operation, Alarm 1, Alarm 2

· Internal/external test/reset button

· Two separate alarm relays, each with 1 changeover contact

· Selectable operating/quiescent current and fault logging

· Continuous self-monitoring

· Multifunctional LCD display

· Password protection for device settings

· Sealable transparent cover

· Spring-loaded terminals (two terminals per connection)

· 2-module housing (36 mm)


Technical Features:


· Version with spring-loaded terminals

· Classification according to IEC 62020, IEC 60755 – Type B

· Power supply configuration: TN / TT systems

· Special firmware suitable for Swiss applications

· Supply voltage: DC 9.6…94 V / AC 16…72 V / 42…460 Hz

· Differential currents: AC, DC, pulsating DC

· Rated frequency: 0 … 2000 Hz

· Response value I n1: 50 … 100%

· Threshold value I n2: 30 mA … 3 A

· 2 alarm relays, each with 1 changeover contact

· For transformers of the W20AB ... W210AB series

· Spring-loaded terminals

· Dimensions: W 36 x H 90 x D 70.5 mm


Applications:


All-current-sensitive residual current monitoring in grounded 2-, 3-, or 4-wire systems (TN and TT systems)

Monitoring of controlled drives, UPS systems, construction machinery, printing presses, battery systems, laboratory equipment, woodworking machines, MF welding systems, the furniture industry, medical equipment, etc.

All-current-sensitive current monitoring of individual conductors that are normally de-energized (e.g., neutral conductor)


Installation orientation:


As specified in the technical manual: Display-oriented = horizontal