B.74014002

RCM420CH-D-2 Differenzstrom Überwachungsgerät

für TN und TT Systeme / V = 70-300 V AC/DC Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

Type A residual current monitoring in accordance with IEC 62020

Alarm without tripping in TN and TT systems

Two separately adjustable response thresholds

Wide frequency range: 42 to 2000 Hz

The RCM420-D (Type A) residual current monitoring device, which is sensitive to alternating and pulsed currents, is used for fault and residual current monitoring in grounded systems (TN and TT systems) where, in the event of a fault, a warning should be issued but the system should not be shut down. It can also be used to monitor individual conductors, such as PE conductors, N-PE bridges, and PE-PAS bridges.


The early warning stage (50…100% of the set response value I∆n2) allows for a distinction between an early warning and an alarm. Since measurement is performed via current transformers, the device is virtually independent of the system’s load current and rated voltage.

Features and Functions:


· Type A residual current monitoring device sensitive to alternating and pulsed currents, in accordance with IEC 62020

· RMS measurement (AC)

· Two independently adjustable response thresholds

· Frequency range 42…2000 Hz

· Adjustable start-up, response, and reset delays

· Restart function

· Digital measurement value display via LCD

· Measurement value memory for trip setpoint

· Connection monitoring for current transducers

· Status LEDs for operation, Alarm 1, Alarm 2

· Internal/external test/reset button

· Two separate alarm relays, each with 1 changeover contact

· Selectable operating/quiescent current and fault memory behavior

· Password protection for device settings

· Device self-monitoring

· Sealable transparent cover

· 2-module housing (36 mm)

· RoHS-compliant

· Spring-loaded terminals (two terminals per connection)


Technical Features:


· Version with plug-in terminals

· Classification according to IEC 60755 – Type A

· Power supply configuration: TN / TT systems

· Special firmware suitable for Swiss applications

· Supply voltage: 70 ... 300 V AC/DC

· Measurement channels: 1

· Differential currents: AC + pulsating DC

· Rated frequency: 42 ... 2000 Hz

· Threshold value I n1: 50 ... 100 %

· Threshold value I n2: 10 mA ... 10 A

· Main alarm relay: 1 changeover contact

· Early warning alarm relay: 1 changeover contact

· Designed for transformers of the W..., WR..., and WS... series

· Dimensions: W 36 x H 90 x D 70.5 mm


Applications:


· Residual current monitoring in grounded 2-, 3-, or 4-wire systems

· Current monitoring of individual conductors that are normally de-energized

· Outlet circuits for devices that are operated unattended for extended periods and must not fail

· Alarm systems, safety devices

· Air conditioning systems, computer systems

· Refrigeration systems containing valuable goods

· Commercial kitchens

· Monitoring of grounded power supplies for stray currents

· Loading on neutral conductors

· Pipe trace heating systems


Note:


When used with electrical or electronic loads containing a DC component, a solution sensitive to all types of current—such as the RCMA423 or an equivalent device—must always be implemented.


Installation orientation:


As specified in the technical manual: Any orientation