CEP410R-2 Differenzstrom Überwachungsgerät
Type A residual current monitoring in accordance with IEC 62020-1
Measurement range: 10 mA to 30 A
RS-485 with Modbus RTU
NFC configuration via the Bender Connect app
This monitoring device, which is sensitive to AC and pulsating DC, can be connected to existing communication networks, enabling remote monitoring of its status. Two separately adjustable thresholds allow for a distinction between an early warning and a main alarm (early warning = 50–100% of the set threshold Idn).
· Type A differential current monitoring device sensitive to alternating and pulsed currents, in accordance with IEC 62020-1
· Root-mean-square (r.m.s.) measurement
· Measurement range: 10 mA…30 A (42…70 Hz)
· Early warning: 50…100% of the trip differential current
· Supply voltage: 24 V DC or 100…240 V AC/DC
· LED strip measurement value display
· Adjustable response delay
· Alarm relay (designed as a changeover contact)
· Selectable active/quiescent current principle and fault memory behavior
· RS-485 with Modbus RTU
· Continuous monitoring of the current transformer connection
· NFC interface for configuring the device while powered on or off via the Bender Connect app