B.84606041

RCMS425-D Differenzstrom-Überwachung

Inklusive aktiviertes Funktionsmodul Typ B Nachkauf der Module A und C ist möglich

4-channel all-current-sensitive differential current monitoring

Measurement range: 2 mA to 70 A, DC up to 20 kHz

Harmonic analysis up to the 400th harmonic

RS-485 interface with Modbus RTU

Compact and high-performance, 4-channel residual current monitor sensitive to DC, AC, and pulsed currents for grounded power supply systems. It measures residual currents between 2 mA and 70 A for DC voltages as well as AC voltages in a frequency range from 15 Hz to 20 kHz, enabling flexible use in a wide variety of applications.

Key Features:


· 4 channels in a compact housing

· Analysis of harmonics up to the 400th harmonic

· Adjustable frequency response


Features and Functions:


· Continuous differential current monitoring

· 4 measurement channels for residual current measurement

· Selectable AC, pulse, or all-current-sensitive measurement

· Continuous connection monitoring of the current transformer

· Separate evaluation of the AC and DC components as well as the root mean square (RMS) value of the differential current is possible

· Selectable overcurrent (standard), undercurrent, or window function per channel

· Each measurement channel can alternatively be configured as a digital input

· Response ranges: 10 mA…10 A (Type B/B+), 6 mA…30 A (Type A/F)

· Frequency range: DC…20 kHz

· Preset function

· Reload function

· Adjustable time delays

· Adjustable frequency response

· Analysis of harmonics up to the 400th harmonic, calculation of the THD value

· One digital input, one digital input/output, and one multifunctional digital/analog output

· Integrated combined test/reset button, connection for external buttons

· One device status LED, two alarm LEDs, and one alarm LED per channel

· RS-485 interface with Modbus RTU (reading measured values/configuration)
-Compatible in a networked system with other Modbus RTU-capable device series from Bender, including the RCMB300 series, RCMS150-01, and RCMB13…-01
-Compatible with Bender gateways of the types COM465IP and CP9…-I
- Up to 247 RCMS410 units can be used on the bus

· NFC interface for parameterization using the Bender Connect app

· Expansion, retrofitting, or modification of functionalities to accommodate changing monitoring requirements

· Complies with DIN EN IEC 62020-1


Compatible current transformer series:

· Type A: CTAC, CTAS, W, WR, WS

· Type F: CTAC

· Type B/B+: CTUB-CTBC, CTBS


Application:

· Measuring and evaluating differential, fault, and rated currents of loads and systems

· Monitoring the residual currents of stationary electrical installations and equipment as an alternative to Rinsulation test in accordance with the DGUV V3 Accident Prevention Regulation and the BetrSichV Industrial Safety Regulation

· Detecting gradual deterioration of insulation supports preventive maintenance

· Monitoring of fire-hazardous currents in fire-prone facilities

· EMC monitoring of TN-S systems for “stray” currents and additional N-PE bridges

· Monitoring of PE and PA conductors to ensure they are free of current

· Monitoring of N conductors for overloading due to harmonics

· Monitoring of digital inputs


Ordering Information:

· Delivery includes activated Function Module B

· Function modules A and C can be purchased separately

· Prices for function modules available upon request


Supply voltage:

· Connections: +, –, A1, A2

· Supply voltage: Us DC 24 V / AC/DC 100…240 V