B.94053004

RCMS460CH-L-2 Differenzstrom Auswertegerät, mehrkanal

Allstromsensitiv, 7-Segment-Anzeige und LED-Zeile Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

Differential current monitoring with 12 measurement channels

Up to 90 devices / 1,080 measurement channels in the system

Selectable sensitivity to alternating, pulsed, or all types of current

Alternative to insulation testing according to DGUV V3

The residual current monitoring system (RCMS system) consists of one or more RCMS460-D/-L or RCMS490-D/-L residual current monitoring devices, which can measure and evaluate fault, residual, and operating currents in grounded power supply systems using the corresponding current transformers. The maximum voltage of the monitored network depends on the rated insulation voltage of the measuring current transformers used in busbar systems or on the cables or conductors installed.


For all-current-sensitive measurement (according to IEC/TR 60755: Type B), the closed-type current transformers of the W…AB series are required. One AN420 or AN110 power supply unit is required for every 6 current transformers of the W…AB series.


For alternating and pulsed currents (according to IEC/TR 60755: Type A), the current transformers of the W… (closed), WR… (rectangular), WS… (splittable), and WF… (flexible) series are used.


The various current transformers can be connected to the measurement channels of the monitoring devices in any combination. Each RCMS460-D/-L and RCMS490-D/-L has 12 measurement channels. A total of up to 90 residual current monitoring devices can be connected via the BMS bus (RS-485 interface with BMS protocol), allowing for the monitoring of up to 1,080 measurement channels (outputs).


The frequency response can be adjusted accordingly for applications in personal, fire, and equipment protection. The measured currents can be analyzed for harmonic distortion.

Key Features:

Alternative to the DGUV V3 insulation test

Optional AC, pulse, or all-current-sensitive measurement by selecting the current transformers for each channel

Preset function

Analysis of harmonics, DC, and THF

Adjustable frequency response for personal, fire, and equipment protection


Features and Functions:

Selectable AC, pulse, or all-current-sensitive measurement by selecting the current transformers for each channel

True root mean square (r.m.s.) measurement

12 measurement channels per unit for differential current measurement or digital input

Up to 90 RCMS… monitoring devices; 1,080 measurement channels in the system

Fast parallel polling for all channels

Measurement ranges: 10 mA…10 A (0…2000 Hz), 6 mA…20 A (42…2000 Hz), 100 mA…125 A (42…2000 Hz) RCMS…-D4

Preset function

Adjustable time delays

Adjustable frequency response for personal, fire, and equipment protection

History memory with timestamps for 300 data records

Data logger for 300 data records per channel

Analysis of harmonics, DC, and THD

Two alarm relays, each with 1 changeover contact

Selectable operating/quiescent current and fault memory behavior

Connection for external reset/test button

Backlit graphic display (7-segment display) and status LEDs

Data exchange via BMS bus

Password protection for device settings

Continuous monitoring of the measuring current transformer connection

RoHS-compliant


Technical Specifications:

Number of measurement channels per device: 12

Special firmware suitable for Swiss applications

External current transformers: Series

W..., WR..., WS..., (Type A), W...AB Series (Type B)

7-segment display for error codes

LED bar for alarms 1 through 12

Dimensions: W 108 x H 90 x D 74 mm

Power supply: DC 70…276 V / AC 70…276 V / 42…460 Hz


Applications:


Measuring and evaluating differential, fault, and rated currents of loads and systems in the frequency range 0…2000 Hz (current transformers W…AB) and 42…2000 Hz (current transformers W…, WR…, WS…, WF…)

Monitoring of fire-hazardous currents in fire-prone facilities

EMC monitoring of TN-S systems for “stray” currents and additional N-PE bridges

Monitoring of N conductors for overloading due to harmonic distortions

Monitoring of PE and PA conductors for the absence of current

Monitoring of residual currents in stationary electrical installations and equipment to determine practical testing intervals in accordance with the Accident Prevention Regulation BGV A3 and the Industrial Safety Ordinance (BetrSichV).

Personal and fire safety through rapid shutdown

Monitoring of digital inputs