B.94043055

MRCDB423-D-1 MRCD TYP B, 24 VDC

Modulares Fehlerstromgerät Typ B

Type B residual current device (RCD) sensitive to all currents, in accordance with DIN EN 60947-2

Operating range: IÄn 30 mA to 3 A

Supply voltage: DC 9.6–94 V / AC 16–72 V

Supplementary protection in grounded TN and TT systems

The all-current-sensitive MRCDB423, together with the corresponding CTUB101-CTBC… current transformers, are used as additional protection (protection against indirect contact) in grounded systems (TN and TT systems) where DC or AC fault currents may occur. These systems include, in particular, loads with six-pulse bridge rectifiers or single-phase rectifiers with smoothing, such as inverters, chargers, and construction machinery with frequency-controlled drives.

Functions and Features:


· All-current-sensitive Type B RCD in accordance with DIN EN 60947-2, Annex M

· Used as a modular residual current protective device

· For additional protection in grounded systems

· Type B response characteristic per IEC 60755

· RMS measurement of the residual current

· Alarm and pre-alarm indication via LEDs

· Alarm and pre-alarm output via relays (K1/K2)

· Control of a switching device with isolating capabilities via relay K2

· Connection monitoring of the measuring current transformer

· Fault memory


Technical Specifications:


· Response range IÄn: 30 mA...3 A

· Rated frequency: 0...2000 Hz

· Supply voltage Us: DC 9.6…94 V / AC 42…460 Hz, 16…72 V



Application:


Additional protection (protection against indirect contact) in grounded systems (TN and TT systems)