B.94053025

RCMS150CH Differenzstrom Auswertegerät

Allstromsensitiv, DC/AC 0..2000Hz 3...300 mA Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

6-Channel Differential Current Monitoring, Type B

All-current-sensitive measurement: DC 0 to 2 kHz

Alternative to insulation testing according to DGUV V3

RS-485 interface with BMS protocol

The RCMS150 six-channel differential current monitor is designed to measure DC and AC fault currents in grounded power supply systems that may arise due to insulation faults in loads equipped with six-pulse bridge rectifiers or single-phase rectifiers with smoothing. The device is capable of measuring differential currents up to IÄ = 500 mA in a frequency range of DC 0…2 kHz. Two separately adjustable threshold values allow for differentiation between an early warning and an alarm.


The device features an RS-485 interface through which measurement and alarm values are transmitted. This interface also allows for parameter configuration.

Key Features:


· Alternative to the ISO test according to DGUV V3

· Type B all-current-sensitive measurement data acquisition

· Pure DC fault analysis

· Can be used in very confined spaces

· RS-485 data from the BMS can be visualized


Functions and Features:


· Continuous residual current monitoring in accordance with DGUV Regulation 3

· All-current-sensitive residual current monitoring device, Type B, with 6 channels K1…6 (each channel provides 2 measurement channels: 1 x RMS, 1 x DC)

· Compatible with RCMS460/490 in a networked system

· Ideal for space-constrained applications

· Easy installation on a top-hat rail or screw mounting on an installation panel

· 2 independently adjustable threshold values (DC or r.m.s.) per channel

· Continuous self-monitoring

· Fully shielded current transformers to prevent interference from disruptive magnetic fields

· Compatible with Bender gateways of the COM465IP and CP700 types

· Up to 534 measurement channels can be combined in the monitored system via the BMS bus

· RS-485 interface with BMS bus (Modbus RTU available upon request)

· BMS address range 2–90


Technical Features:


· Number of measurement channels per device: 6

· Inner diameter: 10 mm

· Power supply: 24 V DC

· Interface: RS485 with BMS protocol

· Special firmware suitable for Swiss applications

· Dimensions: W 245 x H 26 x D 38 mm

· Weight: 340 g


Application:


The RCMS150 is designed to measure differential currents up to IÄ = 500 mA in a frequency range of DC 0…2 kHz. The monitored circuit is rated for a voltage of 300 V and a load current of 32 A. The device can be used at altitudes up to 2,000 m above sea level.


Optional accessory: Power supply R0002554