Shop
RCMS425-L Differenzstrom-Überwachung
4-channel all-current-sensitive differential current monitoring
Measurement range: 2 mA to 70 A, DC up to 20 kHz
Harmonic analysis up to the 400th harmonic
RS-485 interface with Modbus RTU
Compact and high-performance, 4-channel residual current monitor sensitive to DC, AC, and pulsed currents for grounded power supply systems. It measures residual currents between 2 mA and 70 A for DC voltages as well as AC voltages in a frequency range from 15 Hz to 20 kHz, enabling flexible use in a wide variety of applications.
Key Features:
· 4 channels in a compact housing
· Analysis of harmonics up to the 400th harmonic
· Adjustable frequency response
Features and Functions:
· Continuous differential current monitoring
· 4 measurement channels for residual current measurement
· Selectable AC, pulse, or all-current-sensitive measurement
· Continuous connection monitoring of the current transformer
· Separate evaluation of the AC and DC components as well as the root mean square (RMS) value of the differential current is possible
· Selectable overcurrent (standard), undercurrent, or window function per channel
· Each measurement channel can alternatively be configured as a digital input
· Response ranges: 10 mA…10 A (Type B/B+), 6 mA…30 A (Type A/F)
· Frequency range: DC…20 kHz
· Preset function
· Reload function
· Adjustable time delays
· Adjustable frequency response
· Analysis of harmonics up to the 400th harmonic, calculation of the THD value
· One digital input, one digital input/output, and one multifunctional digital/analog output
· Integrated combined test/reset button, connection for external buttons
· One device status LED, two alarm LEDs, and one alarm LED per channel
· RS-485 interface with Modbus RTU (reading measured values/configuration)
-Compatible in a networked system with other Modbus RTU-capable device series from Bender, including the RCMB300 series, RCMS150-01, and RCMB13…-01
-Compatible with Bender gateways of the types COM465IP and CP9…-I
- Up to 247 RCMS410 units can be used on the bus
· NFC interface for parameterization using the Bender Connect app
· Expansion, retrofitting, or modification of functionalities to accommodate changing monitoring requirements
· Complies with DIN EN IEC 62020-1
Compatible current transformer series:
· Type A: CTAC, CTAS, W, WR, WS
· Type F: CTAC
· Type B/B+: CTUB-CTBC, CTBS
Application:
· Measure and evaluate differential, fault, and rated currents of loads and systems
· Monitoring residual currents in stationary electrical systems and equipment as an alternative to RIso testing in accordance with the DGUV V3 Accident Prevention Regulation and the BetrSichV Industrial Safety Regulation
· Detecting gradual deterioration of insulation supports preventive maintenance
· Monitoring of fire-hazardous currents in fire-prone facilities
· EMC monitoring of TN-S systems for “stray” currents and additional N-PE bridges
· Monitoring of PE and PA conductors to ensure they are free of current
· Monitoring of N conductors for overloading due to harmonics
· Monitoring of digital inputs
Ordering Information:
· Shipped with factory settings (production variant)
· Additional function modules A, B, and C can be purchased separately
· Prices for function modules available upon request
Supply voltage:
· Connections: +, –, A1, A2
Supply voltage: Us DC 24 V / AC/DC 100…240 V