B.74603000

RCM410R-2 Differenzstrom Überwachungsgerät

Spannungsversorgung 100…240 V AC/DC Schweizer Standardausführung gemäss NIN Kap.5.3.2.3 SmartDetect

Type A residual current protection in accordance with IEC 62020

Adjustable trip current IÄn from 10 mA to 30 A

Alarm without tripping in TN/TT systems

RS-485 with Modbus RTU, AC/DC power supply 100–240 V

Single-channel, alternating and pulsed current-sensitive residual current monitoring device for AC systems


The RCM410R AC and pulse current-sensitive residual current monitoring device is used for fault or residual current monitoring in grounded systems (TN/TT) where, in the event of a fault, a warning signal should preferably be issued, but the system must not be shut down. It can also be used to monitor individual conductors, such as PE conductors, N-PE bridges, or PE-PAS bridges. Two separately adjustable response thresholds allow for a distinction between an early warning and a main alarm (early warning = 50…100% of the set response residual current IÄn).


Features and Functions


· Type A residual current monitoring device sensitive to alternating and pulsed currents, in accordance with IEC 62020

· Root mean square (r.m.s.) measurement

· Up to 247 monitoring devices in the system

· Adjustable trip differential current IÄn: 10 mA…30 A (42…70 Hz)

· Supply voltage: AC/DC 100…240 V

· LED bar graph display of measured values

· Adjustable response delay

· One alarm relay (changeover contact)

· Selectable operating/standby current and fault memory behavior

· RS-485 with Modbus RTU

· Continuous monitoring of the current transformer connection

Technical Specifications:


· Power supply circuit (IC1) A1, A2

· Output circuit (IC2) 11, 14, 12

· Measurement & control circuit (IC3) S1, S2, +, –, A, B

· Rated voltage 250 V

· Overvoltage category III

· Operating altitude: 2,000 m above sea level

· Rated surge voltage: IC1/(IC2-3) 4 kV / IC2/IC3 4 kV

· Rated insulation voltage: IC1/(IC2-3) 250 V / IC2/IC3 250 V

· Pollution degree 2

· Safe separation (reinforced insulation) between:

· IC1/(IC2-3) Overvoltage Category III, 300 V

· IC2/IC3 Overvoltage Category III, 300 V

· Voltage test (unit test) according to IEC 61010-1:

· IC1/(IC2-3) AC 2.2 kV

· IC2/IC3 AC 2.2 kV

· Operating mode: Continuous operation

· Mounting position: vertical

· Protection class for internal components (DIN EN 60529): IP30

· Protection class of terminals (DIN EN 60529): IP20

· Housing material: polycarbonate

· Quick-mounting on IEC 60715 top-hat rail

· Flammability class: UL94 V-0