RCM410R-2 Differenzstrom Überwachungsgerät
Type A residual current protection in accordance with IEC 62020
Adjustable trip current IÄn from 10 mA to 30 A
Alarm without tripping in TN/TT systems
RS-485 with Modbus RTU, AC/DC power supply 100–240 V
Single-channel, alternating and pulsed current-sensitive residual current monitoring device for AC systems
The RCM410R AC and pulse current-sensitive residual current monitoring device is used for fault or residual current monitoring in grounded systems (TN/TT) where, in the event of a fault, a warning signal should preferably be issued, but the system must not be shut down. It can also be used to monitor individual conductors, such as PE conductors, N-PE bridges, or PE-PAS bridges. Two separately adjustable response thresholds allow for a distinction between an early warning and a main alarm (early warning = 50…100% of the set response residual current IÄn).
Features and Functions
· Type A residual current monitoring device sensitive to alternating and pulsed currents, in accordance with IEC 62020
· Root mean square (r.m.s.) measurement
· Up to 247 monitoring devices in the system
· Adjustable trip differential current IÄn: 10 mA…30 A (42…70 Hz)
· Supply voltage: AC/DC 100…240 V
· LED bar graph display of measured values
· Adjustable response delay
· One alarm relay (changeover contact)
· Selectable operating/standby current and fault memory behavior
· RS-485 with Modbus RTU
· Continuous monitoring of the current transformer connection
Technical Specifications:
· Power supply circuit (IC1) A1, A2
· Output circuit (IC2) 11, 14, 12
· Measurement & control circuit (IC3) S1, S2, +, –, A, B
· Rated voltage 250 V
· Overvoltage category III
· Operating altitude: 2,000 m above sea level
· Rated surge voltage: IC1/(IC2-3) 4 kV / IC2/IC3 4 kV
· Rated insulation voltage: IC1/(IC2-3) 250 V / IC2/IC3 250 V
· Pollution degree 2
· Safe separation (reinforced insulation) between:
· IC1/(IC2-3) Overvoltage Category III, 300 V
· IC2/IC3 Overvoltage Category III, 300 V
· Voltage test (unit test) according to IEC 61010-1:
· IC1/(IC2-3) AC 2.2 kV
· IC2/IC3 AC 2.2 kV
· Operating mode: Continuous operation
· Mounting position: vertical
· Protection class for internal components (DIN EN 60529): IP30
· Protection class of terminals (DIN EN 60529): IP20
· Housing material: polycarbonate
· Quick-mounting on IEC 60715 top-hat rail
· Flammability class: UL94 V-0