RCMB132-01 Differenzstrom-Überwachungsmodul
All-current-sensitive measurement up to ±100 mA
Modbus RTU via RS-485, daisy-chain capable
For installation in PDUs and junction boxes
Frequency range: DC to 2 kHz
All-current-sensitive residual current monitoring module for measuring DC and AC currents up to ±100 mA
The all-current-sensitive differential current monitoring module monitors electrically grounded power supplies up to 300 V and connected loads up to rated currents of 32 A for leakage and fault currents. The module is designed for installation in power distribution equipment such as PDUs (Power Distribution Units), junction boxes, or multi-outlet power strips and is powered by 12–24 V DC.
Features and Functions:
· All-current-sensitive leakage and ground-fault current monitoring for preventive maintenance
· High resolution for implementing device leakage current monitoring
· Measurement value and alarm transmission via Modbus RTU (RS-485)
· Frequency range: DC…2 kHz
· Compact design for monitoring rated loads up to In = 32 A
· Low load current sensitivity due to fully shielded current transformer
· Continuous connection monitoring of the current transformer
· Integrated test function
· Supply voltage: 12–24 V DC
Applications:
The RCMB132-01 is designed for installation in PDUs and distribution boxes. The module
can communicate with a master via a Modbus RTU protocol over an RS-485 interface.
It is possible to connect multiple devices in a daisy chain. To this end,
the RCMB132-01 provides two identical connectors for RS-485 (including power supply)
. Factory settings: RMS 30 mA, DC 6 mA (adjustment range 3.5–100 mA), DC 6 mA (adjustment range 3.5–100 mA).