B.78080204

WF250CH-2 Messstromwandler Flexibel

Differenzstrommessung der Serie RCMS460/490 Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

Flexible current transformer, 250 mm measurement loop

Retrofit without shutting down the system

Measurement range: 100 mA to 20 A

For RCMS460/490 and RCM420, including RCC420-2

The WF… series flexible current transformers are highly sensitive current transformers that convert AC currents into an analyzable measurement signal when used in conjunction with RCMS460/490 series differential current monitoring devices.

They consist of a flexible current transformer W…F and a signal converter RCC420.

The connection to the respective residual current monitoring devices is made via a two-wire cable.

Features and Functions:


· Flexible current transformer available in various lengths

· Space-saving and quick installation

· Easy retrofitting in existing systems

· No need to shut down the system for installation

· Connection monitoring for WF… current transformers

· For residual current monitoring systems of the RCMS460/490 series

· For RCM420 series residual current monitoring devices

· Analog output (U, I) for external measuring devices

· RCC420 with spring-loaded terminals (two terminals per connection)


Technical Specifications:


· 250 mm measurement loop, incl. RCC420-2

· Measurement loop diameter: 79 mm

· Supply voltage Us DC/AC 42...460 / Hz 70...300 V

· Measurement range: 100 mA...20 A

· Rated frequency: 42...2000 Hz

· Rated load: 68 ohms


Applications:


· Differential, fault, and rated current monitoring of loads and systems that cannot be shut down.

· EMC monitoring of TN-S systems for “stray currents” and additional N-PE connections at the central grounding point (ZEP).

· Monitoring of PE and PA conductors to ensure they are current-free.