WF170CH-2 Messstromwandler Flexibel
Flexible current transformer, 170 mm measurement loop
Retrofit without shutting down the system
Measurement range: 100 mA to 20 A
For RCMS460/490 and RCM420, including RCC420
The WF… series flexible current transformers are highly sensitive current transformers that convert AC currents into an analyzable measurement signal when used in conjunction with RCMS460/490 series differential current monitoring devices.
They consist of a flexible current transformer W…F and a signal converter RCC420.
The connection to the respective residual current monitoring devices is made via a two-wire cable.
Features and Functions:
· Flexible current transformer available in various lengths
· Space-saving and quick installation
· Easy retrofitting in existing systems
· No need to shut down the system for installation
· Connection monitoring for WF… current transformers
· For residual current monitoring systems of the RCMS460/490 series
· For RCM420 series residual current monitoring devices
· Analog output (U, I) for external measuring devices
· RCC420 with spring-loaded terminals (two terminals per connection)
Technical Specifications:
· Measurement loop 170 mm, incl. RCC420
· Measurement loop diameter: 54 mm
· Supply voltage: Us DC 70…300 V / AC 42…460 Hz 16…300 V
· Measurement range: 100 mA–20 A
· Rated frequency: 42…2000 Hz
· Rated load: 68 ohms
Applications:
· Differential, fault, and rated current monitoring of loads and systems that cannot be shut down.
· EMC monitoring of TN-S systems for “stray currents” and additional N-PE connections at the central grounding point (ZEP).
· Monitoring of PE and PA conductors to ensure they are current-free.