B.98080003

W20CH Stromwandler für Bender

Differenzialstromrelais, Lochdurchmesser 20 mm Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

Current transformers for RCM, RCMS, and EDS systems

Primary rated differential current: 1 A

Compact design: 76.4 x 56.3 mm

Connection via a two-wire cable

The W… and W…-8000 series current transformers are highly sensitive current transformers that convert AC currents into an analyzable measurement signal when used in conjunction with RCM or RCMS series residual current monitoring devices and systems.


They are also suitable for use with insulation fault locators for IT systems (EDS). They are used to detect the test current generated by a PGH or ISOMETER® IRDH insulation fault tester. The test current is converted into an analyzable measurement signal when used in conjunction with EDS series insulation fault locators.


The connection to the respective devices is made via a two-wire cable.

Applications:


· For RCMS460/490 series residual current monitoring systems

· For RCM420 series residual current monitoring devices

· For EDS440, EDS460, and EDS490 series insulation fault locators


Technical Specifications:


· Primary rated residual current: 1 A

· Secondary rated residual current: 0.125 mA

· Rated load: 2,400 ohms

· Rated power: 0.0375 VA

· Weight: 0.13 kg

· Dimensions: W 76.4 x H 56.3 x D 30 mm


Note:


DIN rail snap-on mounting is not included