B.911733

W3-S105CH Stromwandler für Bender RCM und RCMS

Überwachungsgeräte d. Serie 420/460/470/490 Schweizer Standardausführung gemäss NIN Kap.5.3.2.3

Current transformers for differential currents up to 100 A

Inner diameter 105 mm

Up to 40 m distance to the evaluation unit

For RCM, RCMS, and EDS systems

The W0-S20…W5-S210 current transformers are highly sensitive devices that convert differential currents up to 100 A into analyzable RCM or EDS signals. They are connected to the respective devices via two connecting wires. Depending on the type of cable used, the distance between the current transformer and the analysis unit can be up to 40 m.


It is essential to ensure that all current-carrying wires pass through the current transformer and that these wires are unshielded.

Under no circumstances should an existing protective conductor be routed through the current transformer!

Technical Specifications:


· Inner diameter: 105 mm

· Nominal gear ratio:

· Rated voltage: 800 V

· Primary rated residual current: 10 A

· Rated load: 180 ohms (18 ohms - 10 A)

· Dimensions: W 170 x H 146 x D 33 mm (with DIN foot: 46 mm)

· Mounting feet for rail mounting

· Weight: 425 g


Applications:


· Residual Current Monitors (RCM)

· Residual Current Monitoring Systems (RCMS)

· Earth fault detectors (EDS)