CTBC35P Messstromwandler geschirmt 35 mm
All-current-sensitive residual current monitoring, Type B/B+
MRCD protective device in accordance with DIN EN 60947-2, Annex M
For personal, fire, and equipment protection
RS-485 interface with Modbus RTU
LINETRAXX MRCDB300 Series
The all-current-sensitive MRCDB300 device series is used as additional protection (protection against indirect contact) in grounded systems (TN and TT systems) where DC or AC fault currents may occur. These systems include, in particular, loads with six-pulse bridge rectifiers or single-phase rectification with smoothing, e.g., inverters, chargers, and construction machinery with frequency-controlled drives. When the trip value IÄn2 (alarm) is reached, the output relays K1 and K2 trip.
By using an MRCDB300 module and a switching element with isolating properties, the device combination meets the requirements for an MRCD protective device according to DIN EN 60947-2 Annex M. The application is specifically intended for protection objectives such as personal safety, fire protection, and equipment protection. The switching element must not exceed a maximum trip time of 20 ms. Each residual current monitoring module consists of the MRCDB300 evaluation electronics and a CTBC20(P)…210(P) series current transformer core.
To assemble a complete module, therefore, both the electronics and a current transformer core are required; if ordered separately, these two components must then be connected and calibrated . The CTBC20P…210P series current transformers feature integrated magnetic shielding and are suitable for applications with high load or inrush currents.
Features:
· Design of a protective device in accordance with DIN EN 60947-2, Annex M, in combination with a circuit breaker that has isolating capabilities
· Monitoring of the connected circuit breaker via contact feedback
· RS-485 interface with Modbus RTU (reading measured values/parameterization)
· Integrated switching outputs with two changeover contacts, K1 and K2 (galvanically isolated)
· Meets the protection objectives for personal safety, fire protection, and equipment protection (depending on the variant)
· Frequency range: DC…100 kHz
· Combined test and reset button
· Multicolor LED for operation, threshold exceedance, fault, and status messages
· All-current-sensitive measurement acquisition, Type B, according to IEC 60755
· Type B+ all-current-sensitive measurement according to VDE 0664-400
· Replaceable electronics housing without mechanical separation of the primary conductors
· Expansion, retrofitting, or modification of functionalities to meet changed monitoring requirements
· Load-current-insensitive due to full magnetic shielding (CTBC20P…210P only)
· Connection monitoring of the current transformer using a cyclic test current
· Compatibility of all MRCDB300 units with all CTBC… current transformer sizes
· Supply voltage: 24 V DC
Possible trip thresholds (to be set on the evaluation unit):
· CTBC20, CTBC20P 10 mA…500 mA
· CTBC35, CTBC35P, CTUBC60, CTBC60P 30 mA…10 A
· CTBC120P, CTBC210P 100 mA…10 A
· CTBC120, CTBC210 300 mA…10 A
Commissioning:
· Perform the offset adjustment on the de-energized system.
Current Transformer Core
The appropriate modules must be ordered together with the core.