LINETRAXX VMD461
Monitoring of frequency, undervoltage, and overvoltage
For DC, AC, and 3(N)AC systems
ROCOF, vector jump, and rotating field monitoring
With CD440 coupling device up to 1,200 V
The VMD461 multifunctional voltage monitoring relay monitors frequencies, undervoltages, and overvoltages in DC, AC, and 3(N)AC systems. The phase and/or neutral voltages are measured as root mean square (RMS) values and continuously displayed on the unit’s screen. The measured value used to trigger the alarm relays is stored.
The VMD461 features additional measurement functions for:
· ROCOF df/dt
· Vector jump monitoring
· Unbalance monitoring
· Rotating-field monitoring
. The corresponding ANSI codes are stored for all available measurement functions.
Adjustable delay times allow for specific system characteristics (e.g., device-specific startup phases) to be taken into account. The VMD461 requires a separate power supply.
The optional use of the CD440 coupling device extends the monitorable voltage range to DC/3AC 1200 V or 1AC/3NAC 690 V.
Key Features:
· Voltage monitoring up to 1200 V
· Display of all functions in ANSI codes
· 3-stage voltage and frequency monitoring with response and reset delays
· Can be used in a wide variety of power system configurations, such as AC, 3AC, 3NAC, and DC
Features and Functions:
· When used in conjunction with the CD440 interface unit, DC power systems up to 1200 V, 1AC power systems up to 690 V, 3AC power systems up to 1200 V, and 3NAC power systems up to 690 V can be monitored
· All functions are represented using ANSI codes
· Monitoring of DC, 1AC, and 3(N)AC systems per DIN EN 60255-1:2010-9
· Single-fault immunity
· Monitoring of imbalance, phase loss, and rotating field
· Monitoring of connected (circuit) breakers: configurable: NC/NO/off
· Islanding detection df/dt (ROCOF)
· Vector jump function
· RS-485 interface (data exchange/parameterization/software update)
· Test function for determining the trip time
· Test button for the trip circuit
· Ability to retrieve the last 300 grid faults with timestamps/real-time clock
· Continuous monitoring of phase and neutral voltages
· Separate reclosing conditions following a trip threshold violation
· Language selection (German, English, French)
· Backlit graphic display
· Password protection for device settings
· Remote shutdown via remote control signal receiver
· Sealable housing
Applications:
· Monitoring of voltage-sensitive machines and systems
· Switching systems on and off at or above a certain voltage
· Protection of three-phase motors against phase loss and phase reversal
· Vector jump detection for protecting electric machines
· ROCOF (rate of change of frequency) islanding detection
· Protection of transformers by detecting asymmetric loading
Mounting position:
According to the technical manual: Any orientation