Shop
VME420CH-D-2 Unter- od. Überspannungsrelais
Monitoring of overvoltage, undervoltage, and frequency
For AC/DC systems: 0 to 300 V
Adjustable start-up, response, and reset delays
AC and DC RMS measurement with LC display
The VME420 series voltage relays monitor frequency, undervoltages, overvoltages, and the voltage between two threshold values in AC and DC systems. Voltages are measured as root-mean-square (RMS) values. The current measured value is continuously displayed on the LCD. The measured value used to trigger the alarm relays is stored. Adjustable delay times allow for system-specific characteristics to be taken into account, such as equipment-related startup phases, brief voltage fluctuations, etc.
The VME420 model requires an external power supply.
Key Features:
· Monitoring of under- and overvoltage and frequency in AC/DC systems, 0…300 V
· Various monitoring functions available < U, > U, < f, > f
· Adjustable start-up, response, and reset delays
· Password protection for device settings
· Preset function (automatic basic parameterization)
Features and Functions:
· Monitoring of under- and overvoltage and frequency in AC/DC systems 0…300 V
· Various monitoring functions available < U, > U, < f, > f
· Adjustable start-up, response, and reset delays
· Adjustable switching hysteresis
· RMS measurement (AC + DC)
· Digital measurement display via multifunctional LCD
· Preset function (automatic basic parameterization)
· LEDs for operation, Alarm 1, Alarm 2
· Measurement value memory for trip value
· Continuous self-monitoring
· Internal test/reset button
· Two separate alarm relays, each with 1 changeover contact
· Selectable standby/operating current and fault memory behavior
· Password protection for device settings
· Sealable transparent cover
· 2-module housing (36 mm)
· Spring-loaded terminals (two terminals per connection)
· RoHS-compliant
Technical Features:
· RMS measured values with LC display
· Special firmware suitable for Swiss applications
· Supply voltage: DC 70–300 V / AC 15–460 Hz, 70–300 V
· Nominal line voltage: 0...300 V DC / 15...460 Hz 0...300 V AC
· Display range: 0...300 V AC / DC
· Threshold value: 6–300 V AC / DC
Applications:
· Voltage and frequency monitoring of single-phase machines and systems
· Ground fault monitoring via voltage transformers in medium-voltage networks
· Monitoring of battery systems
· Switching systems on and off at or above a certain voltage
Mounting position:
According to the technical manual: Any orientation