VMD420CH-D-2 Unter- od. Überspannungsrelais
Voltage and frequency monitoring, 3(N) AC, 0 to 500 V
Monitoring of asymmetry, phase loss, and phase sequence
Adjustable delay times and window function
Two separate alarm relays with an LCD display
The VMD420 multifunctional voltage monitoring relays monitor frequencies, undervoltages, overvoltages, and the voltage between two threshold values in 3(N) AC systems. Voltages are measured as root-mean-square (RMS) values. The current measured value is continuously displayed on the LCD. The measured value used to trigger the alarm relays is stored. Adjustable delay times allow for system-specific characteristics to be taken into account, such as equipment-related startup phases, brief voltage fluctuations, etc. The devices require a separate power supply.
Key Features:
· Monitoring of under-voltage, over-voltage, and frequency in 3(N) AC systems, 0…500 V
· Various selectable monitoring functions < U, > U, < f, > f
· Monitoring of asymmetry, phase loss, and phase sequence
· Adjustable start-up, response, and reset delays
Features and Functions:
· Monitoring of undervoltage, overvoltage, and frequency in 3(N) AC systems 0…500 V
· Monitoring of asymmetry, phase loss, and phase sequence
· Various monitoring functions available < U, > U, < f, > f
· Adjustable start-up, response, and reset delays
· Adjustable switching hysteresis
· RMS measurement (AC + DC)
· Digital measurement display via multifunctional LCD
· Preset function (automatic basic parameterization)
· LEDs for operation, Alarm 1, Alarm 2
· Measurement value memory for trip value
· Continuous self-monitoring
· Internal test/reset button
· Two separate alarm relays, each with 1 changeover contact
· Selectable standby/operating current and fault memory behavior
· Password protection for device settings
· Sealable transparent cover
· 2-module housing (36 mm)
· Spring-loaded terminals (two terminals per connection)
· RoHS-compliant
Technical Features:
· RMS measured values with LCD display
· Supply voltage: DC 70...300 V / AC 15...460 Hz, 70...300 V
· Nominal line voltage: 15...460 Hz / 0...500 V 3(N) AC
· Display range: 0...500 V AC
Applications:
· Monitoring of voltage-sensitive machines and systems
· Switching systems on and off at a certain voltage
· Monitoring of emergency or backup power supplies
· Monitoring the line voltage of portable loads
· Protection of three-phase motors against phase failure and phase reversal
· Protection of transformers by detecting asymmetrical loading
Installation orientation:
According to the technical manual: Any orientation