EDS440-S-1 Isolationsfehlersuchgerät ohne LED Display für
Insulation Fault Detection During Operation
12 measurement channels for current transformers
Up to 252 outputs via RS-485 (BS-Bus protocol)
Response sensitivity: 2 to 10 mA
The ISOSCAN EDS44x insulation fault locators are used, in conjunction with the ISOMETER® iso685-D-P or the PGH test current generator, to locate insulation faults in unearthed power supply systems (IT systems).
To do this, they use test current transformers to capture the test current signals generated by the iso685-D-P or IRDH575 insulation monitoring device or the PGH test current generator and evaluate them accordingly. Up to 12 current transformers can be connected to an EDS44x. A total of up to 21 insulation fault detectors can be connected via an RS-485 interface (BS-Bus protocol), allowing up to 252 outputs to be monitored.
Key Features:
· Automated insulation fault detection during operation
· Application: Main circuits
· 12 measurement channels for current transformers
· Transformer connection monitoring
· Universal system concept
Features and Functions:
· Universal system concept
· Modular design, making it easy to adapt to existing conditions
· Current transformers available in various sizes and designs
· Transformer connection monitoring
· 12 measurement channels for W…, WR…, and WS… series current transformers
· Selectable error logging behavior
· Configuration options allow for customization
· Up to 21 EDS insulation fault locators in the system, 252 measurement channels
· Response sensitivity 2…10 mA
· AC differential current measurement with adjustable threshold
· Two alarm relays, each with one normally open contact
· Selectable operating/quiescent current
· External test/reset button via digital inputs
· Display via ISO 685-D-P or LED display
· Centralized display of faulty outputs
· RS-485 serial interface, BS-Bus address range 2…90
· Connection to higher-level control and visualization systems possible
Technical Specifications:
· Connection type: pluggable screw or spring-loaded terminal
· Rated insulation voltage: (IEC 60664-1) 250 V AC
· Supply voltage range Us: AC/DC 24…240 V
· Threshold value for insulation fault detection (IÄL) EDS440: 2…10 mA
· Digital inputs: 2
· Digital current output: 1
· Buzzer: 1
· Interface/protocol: RS-485/BS
· Relays: 2 normally open
· Data rate: 9600 baud/s
· Dimensions (W x H x D): 72 x 93 x 63 mm
Applications:
· Insulation fault detection in AC, 3AC, and DC IT systems
· Main and control circuits in industrial plants and ships
· Diode-decoupled DC IT systems in power plants
· Power systems for medical facilities