B.91065100

IRDH275-435 A-Isometer

Isolationsüberwachungsgerät Lieferbar solange Vorrat

Insulation Monitoring for IT Systems: AC 0–793 V, DC 0–650 V

AMPPlus measurement method in accordance with DIN EN 61557-8

Two independently adjustable threshold values: 1 kOhm–10 MOhm

History log with real-time clock

The ISOMETER® IRDH275 series monitors the insulation resistance of ungrounded main circuits (IT systems) operating at AC, AC/DC 0…793 V, or DC 0…650 V. Thanks to the AMPPlus measurement method, they are particularly well-suited to the requirements of modern power supply systems, which often include inverters, power converters, thyristor controllers, and directly connected DC components. Due to EMC suppression measures, these systems often also feature high leakage capacitance to ground, which the IRDH275 accounts for by automatically adjusting to optimize the measurement time.


When used in conjunction with a coupling device, the units can also be employed for higher voltages. The isolated power supply allows for monitoring of the de-energized system. For installation in distribution panel doors, see model IRDH375(B).

Key Features:


· Insulation monitoring device for AC and DC IT systems

· Application: Main circuits with connected frequency converters

· Complies with DIN EN 61557-8

· Automatic adaptation to grid leakage capacitance

· Info button for displaying device settings


Features and Functions:


· Insulation monitoring for unearthed systems: AC, AC/DC 0…793 V, DC 0…650 V

· Rated voltage expandable via coupling device

· Two independently adjustable threshold values: 1 kΩ…10 MΩ

· AMPPlus measurement method

· Automatic adaptation to line leakage capacitance

· Info button for displaying device settings and line leakage capacitance

· Self-monitoring with automatic notification

· Selectable automatic self-test

· Connection for external kÙ display

· Test and reset button

· Connection for external test/reset button

· Two separate alarm relays with two potential-free changeover contacts

· Selectable between active and passive current switching

· Backlit plain-text display

· RS-485 interface


Technical Specifications:


· For ungrounded systems: AC, AC/DC 0...793 V, DC 0...650 V

· AMP measurement method,

· Rated voltage expandable via coupling device

· History function with real-time clock for storing alarm messages with date and time

· Rated voltage: AC 800 V

· Nominal line voltage: AC 0...793 V / DC 0...650 V

· Supply voltage: AC 88...264 V / DC 77...286 V


Applications:


· AC, DC, or AC/DC main circuits

· AC/DC main circuits with directly connected DC components such as power converters,

· inverters, thyristor-controlled DC drives

· UPS systems, battery networks

· Heating devices with phase-angle control

· Systems with switching power supplies

· IT systems with high leakage capacitance

· Coupled IT systems