Shop
isoRW425-D4W-4 A-Isometer mit Impedanzüberwachung
AC/DC power supplies up to 400 V
Threshold value 1–990 kOhm
LCD display
Spring-loaded terminal connection
The ISOMETER monitors the insulation resistance (R-Mode) or insulation impedance (Z-Mode) of ungrounded AC/DC main circuits (IT systems) with nominal line voltages of 3(N)AC, AC, AC/DC, or DC 0…440 V. The DC-powered components present in 3(N)AC and AC/DC systems do not affect the response behavior as long as at least a DC load current of 10 mA is flowing. Thanks to the separate supply voltage, it is also possible to monitor a de-energized system. The maximum permissible network leakage capacitance Ce is 300 µF in R-Mode and 1 µF in Z-Mode.
Nominal mains voltage Un: DC/AC 15...460 Hz, 0...400 V
Response value R-alarm: 1...990kΩ, RI: 120kΩ
Mains leakage capacitance Ce: < 300 μF
Supply voltage Us: AC 100...240V DC 24...240V
2 NO contacts, LC display, additional processing "W" extended
Climatic and mechanical stresses
Connection with spring terminals