B.71036325

isoGEN423 D4-4 Isometer

Isolationsüberwachungsgerät für mobile Stromerzeuger

Insulation monitoring for IT systems up to 400 V

In accordance with DIN VDE 0100-551 and DIN EN 61557-8

Two adjustable threshold values: 5–200 kΩ

RS-485 with Modbus RTU, BMS, and IsoData

The ISOMETER monitors the insulation resistance of ungrounded AC, AC/DC, and DC systems (IT systems) with nominal line voltages of 3(N)AC, AC/DC 0…400 V, or DC 0…400 V. The maximum permissible line leakage capacitance Ce is 5 µF. The DC-powered components present in AC systems have no effect on the response behavior if a load current of at least DC 10 mA is flowing. Thanks to the separate supply voltage, it is also possible to monitor a de-energized system.

Key Features:


· Insulation monitoring device for portable power generators

· Protective separation with insulation monitoring and shutdown

· Complies with DIN VDE 0100-551 and DIN EN 61557-8

· Two trip thresholds (factory settings: 46 kΩ, 23 kΩ)


Features and Functions:


· Insulation resistance monitoring for ungrounded AC/DC systems

· Measurement of line voltage (true r.m.s.) with under-/overvoltage detection

· Measurement of DC voltages between line and ground (L1+/PE and L2-/PE)

· Two operating modes: GEn and DC

· Automatic adaptation to line leakage capacitance up to 5 µF

· Adjustable start-up, response, and reset delays

· Two separately adjustable response value ranges from 5…200 kΩ (Alarm 1, Alarm 2)

· Alarms are indicated via LEDs (AL1, AL2), a display, and alarm relays (K1, K2)

· Automatic device self-test with connection monitoring

· Selectable relay operating mode (standby or active)

· Measurement value display via multifunctional LCD

· Error logging can be enabled

· RS-485 (galvanically isolated) with the following protocols:
– BMS interface (Bender measuring instrument interface) for data exchange with other Bender components
– Modbus RTU
– IsoData (for continuous data output)

· Password protection against unauthorized changes to parameters


Applications:

· AC main circuits up to 400 V

· DC main circuits up to 400 V

· Generators compliant with DIN VDE 0100-551