iso685-S Isolationsüberwachungsgerät
Insulation monitoring for IT systems in accordance with IEC 61557-8
Universal for AC, 3(N)AC, AC/DC, and DC systems
Two response value ranges: 1 kΩ to 10 MΩ
Integrated web server and Modbus TCP/RTU
The ISOMETER® iso685 is an insulation monitoring device for IT systems in accordance with IEC 61557-8. It can be used universally in AC, 3(N)AC, AC/DC, and DC systems. In AC systems, there may also be extensive DC-powered system components (e.g., power converters, inverters, controlled drives).
iso685-S:
The iso685-S model has no display and no control unit. It can be used in
used in combination with the FP200 and is operated indirectly through it.
Parameterization can also be performed via a web browser or a COM465.
“W” Option
Optionally, the device variants are available in the “W” option for extreme climatic and
mechanical stresses.
Key features:
· Predefined measurement profiles
· Reliable measurement of insulation resistance, voltage, capacitance, and frequency
· Integrated web server
· Modbus TCP/RTU
· History log
Features and Functions:
· ISOMETER® for IT AC systems with galvanically isolated rectifiers or inverters and for IT DC systems (IT = unearthed systems)
· The operating range of the nominal line voltage Un can be extended using coupling devices.
· Automatic adaptation to the existing network shunt capacitance
· Combination of AMPPlus and other profile-dependent measurement methods
· Two separately adjustable response value ranges from 1 kÙ…10 MÙ for Alarm 1 and Alarm 2
· High-resolution graphical LCD display for easy reading and monitoring of the device status
· Connection monitoring (monitoring of the measurement leads)
· Automatic device self-test
· Graphical display of insulation trends over time (isoGraph)
· History memory with real-time clock (3-day buffer) for storing 1,023 alarm messages with date and time
· Current or voltage output 0(4)…20 mA, 0…400 µA, 0…10 V, 2…10 V (galvanically isolated), proportional to the measured insulation value of the network
· Freely programmable digital inputs and outputs
· Remote configuration via the Internet or intranet (web server/option: COMTRAXX® Gateway)
· Worldwide remote diagnostics via the Internet (provided only by Bender Service)
· RS-485/BS (Bender Sensor Bus) for data exchange with other Bender components
· BCOM, Modbus TCP/RTU, and web server
Technical Specifications:
· Supply voltage Us: AC 100…240 V - DC 120…240 V
· Frequency range Us: 50 Hz, 60 Hz
· Monitored IT system:
· - Nominal line voltage Un: AC 0…690 V (0…600 V UL)
· - Nominal grid voltage Un: DC 0…1000 V (0…600 V UL)
· Threshold value Ran1 (Alarm 1): 1 kΩ…10 MΩ (10 kΩ)
· Threshold value Ran2 (Alarm 2): 1 kΩ…10 MΩ (40 kΩ)
· Graphic display, 127 x 127 pixels, 40 mm x 40 mm
· Digital inputs: 3 / Digital outputs: 2
· Analog output: 1
· Interfaces: Ethernet-TCP/IP/HTTP / RS-485 / BMS
· Dimensions: (W x H x D) 107.5 mm x 100 mm x 110 mm
Applications:
· AC, DC, or AC/DC main power circuits
· AC/DC main circuits with directly connected DC components such as power converters, inverters, and controlled drives
· UPS systems, battery networks
· Heating devices with phase-angle control
· Systems with switching power supplies
· IT systems with high leakage capacitance
Installation orientation:
As specified in the technical manual: Front-facing; cooling slots must be ventilated vertically