iso415R-2 A-Isometer SmartDetect 100...240V AC/DC
Insulation monitoring in accordance with IEC 61557-8 and IEC 60364-4-41
For ungrounded AC, AC/DC, and DC systems
Configuration via NFC using the Bender Connect app
RS-485 with Modbus RTU, only 18 mm wide
The ISOMETER iso415R is a simple and intelligent insulation monitoring device designed to ensure electrical safety in control circuits and other applications. It is designed for use in unearthed systems and meets the requirements of the IEC 60364-4-41 and IEC 61557-8 standards. It stands out for its ease of use, wide range of interfaces, flexible application options, and compact design. It is the first device in Bender’s new SmartDetect series and offers maximum safety in unearthed AC, AC/DC, and DC systems.
Device Features:
· Monitoring of insulation resistance for ungrounded 3(N) AC, AC, and DC systems with galvanically connected rectifiers
· Automatic adaptation to the network leakage capacitance up to 25 ìF
· Response time ≤ 6 s at Ce = 1 μF and Rf = Ran/2
· Automatic device self-test with connection monitoring
· Two separately adjustable response value ranges from 5 kΩ to 1000 kΩ
· Alarms are indicated via LEDs (AL1, AL2) and an alarm relay
· Selectable relay operating mode: standby or active 1
· Adjustable start-up, response, and reset delays 1
· Fault memory 1
· RS-485 interface with Modbus RTU protocol
· NFC interface
Technical Features:
· Supply voltage Us AC/DC 100...240 V
· Rated line voltage Un 3(N) AC, AC, DC 100…240 V
· Threshold value Ran1 10…1000 kΩ (40 kΩ)
· Response value Ran2 5…700 kΩ (10 kΩ)
· Status LED display including LED bar graph (7 LEDs)
· Protocol: Modbus RTU
· Dimensions (WxHxD): 18x109x64 mm
Easy configuration via app:
Using the NFC function and the Bender Connect app, you can easily configure the iso415R via a smartphone
Installation orientation:
Cooling slots must be ventilated vertically
Correct supply voltage:
Applying a supply voltage Us that is too high can destroy the device