B.71016305

IR423-D4-2 A-Isometer

Isolationsüberwachungsgerät für IT-Systeme

Insulation Monitoring for Portable Generators

AC systems from 0 to 300 V in accordance with DIN VDE 0100-551

Two separately adjustable trip thresholds

W version for increased mechanical stress

The ISOMETER IR423 monitors the RF insulation resistance of an ungrounded AC system ranging from 0 to 300 V relative to ground, which is powered by a mobile power generator in accordance with DIN VDE 0100-551 (VDE 0100-551). The IR423 is suitable for AC systems with operating frequencies of ≥ 30 Hz and any DC components present. The permissible network leakage capacitance (Cemax) is 5 µF.

Functions and Features:


· Insulation monitoring for mobile power generators, AC 0–300 V

· Protective separation with insulation monitoring and shutdown

· W version for increased mechanical stress

· Two separately adjustable trip thresholds

· Mains/ground connection monitoring

· Operation LED, alarm LEDs: Alarm 1, Alarm 2

· Internal/external test/reset button

· Two separate alarm relays (one changeover contact each)

· Selectable operating/quiescent current

· Selectable fault logging

· Self-monitoring with automatic notification

· Multifunctional LCD display

· Adjustable response delay

· 2-module housing (36 mm)

· Spring-loaded terminals (two terminals per connection)


Technical Specifications:


· Rated line voltage: AC 30...460 Hz, 0...300 V

· Rated voltage: 250 V

· Supply voltage: DC/AC 30...460 Hz, 70...300 V

· Threshold value: 10...200 kΩ

· 2 dry-contact alarm relays

· Two alarm LEDs



Applications:


· IEC 60364-7-717, DIN VDE 0100-717 (2005) Electrical installations on vehicles or in portable units

· DIN VDE 0100-551 (VDE 0100-551), IEC 60364-5-551 Low-voltage power generation systems (mobile power generators)

· GW 308 “Mobile Power Generators for Pipeline Construction Sites 8/00” (DVGW)

· BGI 867 Selection and Operation of Emergency Power Generators at Construction and Installation Sites