IR420-D4-1 A-Isometer
Insulation Monitoring for AC Control Circuits 0–300 V
In accordance with DIN EN 61557-8
Two independently adjustable threshold values: 1–200 kOhm
Monitoring even in de-energized systems
The ISOMETER® IR420-D4 monitors the insulation resistance of unearthed AC control circuits (IT systems) ranging from 0 to 300 V. If the systems being monitored contain DC voltage components—such as those found in switching power supplies or solenoid valves—this may cause distortions in the display and response behavior.
The display and response values apply to pure AC systems.
A separate supply voltage also allows monitoring of the de-energized system.
Key Features:
· Insulation monitoring device for AC IT systems
· Application: Control circuits
· Complies with DIN EN 61557-8
· Two independently adjustable threshold values
· Multifunctional LCD display
Features and Functions:
· Insulation monitoring for IT control circuits, AC 0…300 V
· Two independently adjustable trip thresholds
· Preset function (automatic basic parameterization)
· System/ground connection monitoring
· Status LEDs for operation, Alarm 1, Alarm 2
· Internal/external test/reset button
· Two separate alarm relays (one changeover contact each)
· Selectable operating/quiescent current
· Selectable fault logging
· Self-monitoring with automatic notification
· Multifunctional LCD display
· Adjustable response delay
· 2-module housing (36 mm)
· RoHS-compliant
· Spring-loaded terminals (two terminals per connection)
Technical Specifications:
· Supply voltage Us: AC 16...72 V / DC 9.6...94 V
· For ungrounded AC control circuits
· AC 0 ... 300 V
· Threshold values (Alarm 1): 1 to 200 kΩ
· Threshold values (Alarm 2): 1 to 200 kΩ
· System/ground connection monitoring
· Rated frequency 42–460 Hz
· Rated voltage: AC 250 V
Applications:
· AC control circuits in industry, mechanical engineering, power plants, elevators, automation, etc.
· AC control and auxiliary circuits in accordance with DIN EN 60204-1 “Electrical Equipment of Machines,” IEC 60204-1, EN 60204-1
· AC auxiliary circuits in accordance with DIN VDE 0100-725 (VDE 0100-725)
· Smaller AC IT systems, e.g., lighting systems, mobile power generators