EDS441 Isolationsfehlersuchgerät
Automated insulation fault detection during operation
12 measurement channels for current transformers
Up to 50 EDS devices in the system, 600 measurement channels
RS-485 interface with Modbus RTU
The ISOSCAN® EDS441 insulation fault locators are used, in conjunction with the ISOMETER® iso685-D-P or the PGH test current generator, to locate insulation faults in unearthed power supply systems (IT systems).
Key Features:
· Automated insulation fault detection during operation
· Application: Control circuits
· 12 measurement channels for current transformers
· Transformer connection monitoring
· Universal system concept
Functions and Features:
· Universal system concept
· Modular design, making it easy to adapt to existing conditions
· Current transformers available in various sizes and designs
· Transformer connection monitoring
· 12 measurement channels for CTAC…, WR…, and WS… series current transformers
· Optional expansion with 12 relay channels
· Selectable fault memory behavior
· Up to 50 EDS insulation fault locators in the system, 600 measurement channels
· Response sensitivity: 0.2…1 mA
· AC differential current measurement with adjustable threshold
· Two alarm relays, each with one normally open contact
· Selectable operating/quiescent current
· External test/reset button
· Central display of faulty outputs
· RS-485 serial interface, BS-Bus address range 2–79, Modbus RTU
· Can be connected to higher-level control and visualization systems
Applications:
· Insulation fault detection in AC, 3AC, and DC IT systems
· Main and control circuits in industrial plants and ships
· Diode-decoupled DC IT systems in power plants
· Power systems for medical facilities